Normally closed operation.
Application e.g. limit switches and long cables.
Main benefits comparing to electromechanical relays and opto coupled relays:
- No limited lifetime even with difficult loads, 10 year warranty
- High tolerance against noises
- Guaranteed switching on- and off-levels
- 100 % clear status indication
- Relatively high transient protection
- Extreme reliability
- No need for over dimension of the relay, all values are effective values
- No minimum load requirement
Primary | SLI 250CRI | ||
Input voltage | nominal | VDC | 220...250 |
Input current at nominal voltage | typical | mA | 3,7 |
maximum | mA | 4,0 | |
Input voltage range | minimum | VDC | 190 |
maximum | VDC | 265 | |
Input impedance | typical | kΩ | 68 |
Switch-on voltage | typical | VDC | 170 |
maximum | VDC | 190 | |
Switch-off voltage | typical | VDC | 110 |
minimum | VDC | 80 | |
Secondary | SLI 250CRI | ||
Load voltage | minimum | VDC | 0 |
maximum | VDC | 60 | |
Load current | maximum | mA | 100 |
Voltage drop at 30 mA load | typical | VDC | 0,3 |
maximum | VDC | 0,5 | |
Switch-on delay | typical | ms | 1 |
Switch-off delay | typical | ms | 1 |
Leakage current (on-state) | maximum | µA | 10 |