Relay search

Twitter
Delcon: 
I have 10 new followers from Spain, and more last week. See https://t.co/bTyoqR515o https://t.co/aV9U9Ae5or
Delcon: 
I have 11 new followers from UK., and more last week. See https://t.co/bTyoqR515o https://t.co/FknMK6SBYu

SLO 120CRA

For inductive loads and high DC voltages.
Application e.g. all type of DC-loads.

Main benefits comparing to electromechanical relays and opto coupled relays:

- No limited lifetime even with difficult loads, 10 year warranty
- Handles inductive loads and high DC-loads without extra protection elements
- High tolerance against noises
- Guaranteed switching on- and off-levels
- 100 % clear status indication
- Relatively high transient protection
- Extreme reliability
- No need for over dimension of the relay, all values are effective values
- No minimum load requirement

Datasheet 3D files
Qualifications checkbox_on CE checkbox_on RoHS checkbox_on cULus Listed Ind. Cont. Eq. checkbox_on EAC
Delcon
MTTF (Mean Time To Failure): 30,8 years
PrimarySLO 120CRA
Input voltagenominalVDC120
Input currenttypicalmA3,5
maximummA4,0
Input voltage rangeminimumVDC95
maximumVDC140
Input impedancetypical34
Switch-on voltagetypicalVDC80
maximumVDC95
Switch-off voltagetypicalVDC60
minimumVDC50
SecondarySLO 120CRA
Load voltageminimumVDC0
nominalVDC250
maximumVDC300
Load currentmaximumA1,8
Voltage drop at maximum loadtypicalVDC1
Switch-on delaytypicalms0,5
maximumms1
Switch-off delaytypicalms0,5
maximumms1
Load inductance at 250 V 1,8 A, L/Rmaximumms10
Load inductance at 24 V 1,8 A, L/Rmaximumms100
Leakage current (off-state)maximummA1
Accessories: