SLO 48CRX

Application e.g. resistive loads and high currents (max 10 A).
When using separate mounting base max. current 8 A.
When higher than 8 A needed then select type SLO 48CRXSN
.

Main benefits comparing to electromechanical relays and opto coupled relays:

- No limited lifetime even with difficult loads, 10 year warranty
- High tolerance against noises
- Guaranteed switching on- and off-levels
- 100 % clear status indication
- Relatively high transient protection
- Extreme reliability
- No need for over dimension of the relay, all values are effective values
- No minimum load requirement

 

 

Datasheet 3D files
Qualifications checkbox_on CE checkbox_on cULus Listed Ind. Cont. Eq. checkbox_on EAC
Delcon
MTTF (Mean Time To Failure): 33,1 years
PrimarySLO 48CRX
Input voltagenominalVDC48
Input currenttypicalmA3,5
maximummA4,0
Input voltage rangeminimumVDC35
maximumVDC60
Input impedancetypical13
Switch-on voltagetypicalVDC30
maximumVDC35
Switch-off voltagetypicalVDC25
minimumVDC20
SecondarySLO 48CRX
Load voltageminimumVDC0
nominalVDC24
maximumVDC32
Load currentmaximumA10
Voltage drop at maximum loadtypicalVDC0,3
Switch-on delaytypicalms0,5
maximumms1
Switch-off delaytypicalms0,5
maximumms1
Load inductance at 32 V 10 A, L/Rmaximumms0,5
Load inductance at 24 V 5 A, L/Rmaximumms2
Leakage current (off-state)maximummA1
Accessories: