DIN-rail relay for resistive loads and high currents up to 10 A.
Main benefits comparing to electromechanical relays and opto coupled relays:
- No limited lifetime even with difficult loads, 10 year warranty
- High tolerance against noises
- Guaranteed switching on- and off-levels
- 100 % clear status indication
- Relatively high transient protection
- Extreme reliability
- No need for over dimension of the relay, all values are effective values
- No minimum load requirement
Primary | SLO 48CRXSN | ||
Input voltage | nominal | VDC | 48 |
Input current | typical | mA | 3,5 |
maximum | mA | 4 | |
Input voltage range | minimum | VDC | 35 |
maximum | VDC | 60 | |
Input impedance | typical | kΩ | 13 |
Switch-on voltage | typical | VDC | 30 |
maximum | VDC | 35 | |
Switch-off voltage | typical | VDC | 25 |
minimum | VDC | 20 | |
Secondary | SLO 48CRXSN | ||
Load voltage | minimum | VDC | 0 |
nominal | VDC | 24 | |
maximum | VDC | 32 | |
Load current | maximum | A | 10 |
Voltage drop at maximum load | typical | VDC | 0,3 |
Switch-on delay | typical | ms | 0,5 |
maximum | ms | 1 | |
Switch-off delay | typical | ms | 0,5 |
maximum | ms | 1 | |
Load inductance at 32 V 10 A, L/R | maximum | ms | 0,5 |
Load inductance at 24 V 5 A, L/R | maximum | ms | 2 |
Leakage current (off-state) | maximum | mA | 1 |