SLO 5CRX

Application e.g. resistive loads and high currents (max 10 A).
When using separate mounting base max. current 8 A.
When higher than 8 A needed then select type SLO 5CRXSN
.

Main benefits comparing to electromechanical relays and opto coupled relays:

- No limited lifetime even with difficult loads, 10 year warranty
- High tolerance against noises
- Guaranteed switching on- and off-levels
- 100 % clear status indication
- Relatively high transient protection
- Extreme reliability
- No need for over dimension of the relay, all values are effective values
- No minimum load requirement

 

Datasheet 3D files
Qualifications checkbox_on CE checkbox_on RoHS checkbox_on cULus Listed Ind. Cont. Eq. checkbox_on EAC
Delcon
MTTF (Mean Time To Failure): 34,2 years
PrimarySLO 5CRX
Input voltagenominalVDC5
Input currenttypicalmA12
maximummA15
Input voltage rangeminimumVDC3
maximumVDC7
Input impedancetypical0,42
Switch-on voltagetypicalVDC2,7
maximumVDC3
Switch-off voltagetypicalVDC2,5
minimumVDC2,0
SecondarySLO 5CRX
Load voltageminimumVDC0
nominalVDC24
maximumVDC32
Load currentmaximumA10
Voltage drop at maximum loadtypicalVDC0,3
Switch-on delaytypicalms0,3
maximumms0,5
Switch-off delaytypicalms0,3
maximumms0,5
Load inductance at 32 V 10 A, L/Rmaximumms0,5
Load inductance at 24 V 5 A, L/Rmaximumms2
Leakage current (off-state)maximummA1