Zone 2, gas atmospheres
The published ATEX marking is II 3G Ex nA IIC Gc for the documented relay-and-socket assembly. It does not cover Zone 0 or Zone 1.
Engineering guide · Hazardous locations
Delcon EXI input relays and EXO output relays provide galvanically isolated PLC interfaces for specific hazardous-location installations. Certification applies only to the documented relay-and-socket combination, installation conditions and electrical limits.

The published ATEX marking is II 3G Ex nA IIC Gc for the documented relay-and-socket assembly. It does not cover Zone 0 or Zone 1.
An EXI or EXO relay is used with the matching Ex-approved MIS or MOS socket named in the product documentation.
Certification of a component does not certify the whole panel, machine or process. The system designer remains responsible for the complete installation.
Quick answer
ATEX Directive 2014/34/EU governs equipment and protective systems intended for potentially explosive atmospheres in the EU. IECEx is an international conformity-assessment system based on IEC standards. For Delcon Ex relays, the current product documentation defines the marking, permitted combination, ambient conditions, wiring and electrical ratings.
Published ATEX marking for the documented Delcon Ex relay-and-socket combination. Always verify the exact current datasheet and certificate for the selected model before design release.
Certified assembly
Delcon separates the PLC-side function into input and output families. Select the electrical function first, then verify the exact relay model, mating socket and all installation conditions from the current documentation.
| Function | Relay family | Required socket family | Example products | Published approvals |
|---|---|---|---|---|
| Field signal to PLC input | EXI solid-state input relays | MIS Ex-approved input sockets | EXI24CH + MIS1CCNEX | ATEX, IECEx and cULus HazLoc when assembled and installed as documented. |
| PLC output to field load | EXO solid-state output relays | MOS Ex-approved output sockets | EXO24CHX + MOS1CCNEX | ATEX, IECEx and cULus HazLoc when assembled and installed as documented. |
| High-voltage inductive DC load | EXO CHA4 output relays | MOS Ex-approved output sockets | EXO24CHA4 + MOS1CCNEX | Use only within the model-specific load, ambient and installation limits. |
Published certificate references in the linked Delcon datasheets: DEMKO 13 ATEX 1041005U, IECEx ULD 13.0006U and cULus HazLoc file E332493.
Where the interface fits
Interface PLC I/O with valves, contactors, alarms and field signals in gas-classified package units, subject to the complete equipment design.
Provide galvanic isolation and solid-state switching for auxiliary controls, status signals and actuator circuits in documented Zone 2 installations.
Use certified relay-and-socket combinations in suitable enclosures where the installation classification and applicable marine requirements are separately addressed.
Selection workflow
Confirm zone, gas group, temperature conditions and the applicable regulatory scheme.
Record control signal, load voltage, current, inrush, inductance and switching frequency.
Select EXI + MIS for inputs or EXO + MOS for outputs using the exact documented models.
Apply enclosure, wiring, spacing, fusing, temperature and socket-retention instructions.
Review the current certificate, datasheet, marking and complete equipment conformity file.
Engineering checklist
Area classification: zone, gas group and required equipment protection level.
Ambient conditions: minimum/maximum temperature and heat inside the enclosure.
PLC side: input/output voltage, available current, diagnostics and leakage.
Field side: voltage, current, inrush, power factor or L/R and suppression.
Mechanical installation: enclosure, DIN rail, spacing, socket and captive screw.
Documentation: exact model revision, certificate, datasheet and equipment file.
Frequently asked questions
No. The published marking II 3G / Gc is intended for Zone 2 gas applications under the documented conditions. It does not cover Zone 0 or Zone 1.
Not as an Ex-approved assembly unless that exact socket is explicitly included in the current relay documentation. Use the specified Ex-approved MOS socket for EXO output relays and MIS socket for EXI input relays.
No. The published protection concept is Ex nA / non-sparking, not Ex i intrinsic safety. If an intrinsically safe circuit is required, the complete loop needs a suitable Ex i design and assessment.
No. They document conformity for the certified component and conditions stated in the certificate. The manufacturer of the complete equipment remains responsible for enclosure, wiring, temperature, other components and final conformity assessment.
The “U” suffix identifies an Ex component certificate. The component is intended to be incorporated into complete equipment and used according to its conditions of certification.
Keep the current relay and socket datasheets, certificates, markings, electrical calculations, temperature assessment, wiring diagram, component list and the complete equipment conformity assessment.
Primary references
Delcon can help identify the correct EXI/EXO relay and MIS/MOS socket combination for technical review.