Engineering guide · Hazardous locations

ATEX and IECEx solid-state relays for Zone 2

Delcon EXI input relays and EXO output relays provide galvanically isolated PLC interfaces for specific hazardous-location installations. Certification applies only to the documented relay-and-socket combination, installation conditions and electrical limits.

Delcon EXI and EXO solid-state relays for hazardous locations
Use an approved EXI/EXO relay with its specified Ex-approved MIS/MOS mounting socket.

Zone 2, gas atmospheres

The published ATEX marking is II 3G Ex nA IIC Gc for the documented relay-and-socket assembly. It does not cover Zone 0 or Zone 1.

Relay + socket are one selection

An EXI or EXO relay is used with the matching Ex-approved MIS or MOS socket named in the product documentation.

The complete installation still matters

Certification of a component does not certify the whole panel, machine or process. The system designer remains responsible for the complete installation.

Quick answer

What do ATEX and IECEx approval mean for a relay interface?

ATEX Directive 2014/34/EU governs equipment and protective systems intended for potentially explosive atmospheres in the EU. IECEx is an international conformity-assessment system based on IEC standards. For Delcon Ex relays, the current product documentation defines the marking, permitted combination, ambient conditions, wiring and electrical ratings.

What the published marking states

  • II: equipment group for non-mining applications.
  • 3G / Gc: equipment protection level intended for Zone 2 gas applications under the documented conditions.
  • Ex nA: non-sparking protection concept stated in the published product documentation.
  • IIC: gas group stated on the certificate and datasheet.

What it does not state

  • It does not make a standard PLC output intrinsically safe.
  • It does not permit use in Zone 0 or Zone 1.
  • It does not replace enclosure, spacing, wiring or temperature requirements.
  • It does not approve the complete machine, cabinet or safety function.
II 3G Ex nA IIC Gc

Published ATEX marking for the documented Delcon Ex relay-and-socket combination. Always verify the exact current datasheet and certificate for the selected model before design release.

Important component-certificate limitation: the published ATEX and IECEx certificate numbers end with “U”, indicating an Ex component certificate. The component must be installed and assessed as specified within the complete equipment or protective system.

Certified assembly

Match the relay series to the correct Ex-approved socket

Delcon separates the PLC-side function into input and output families. Select the electrical function first, then verify the exact relay model, mating socket and all installation conditions from the current documentation.

Function Relay family Required socket family Example products Published approvals
Field signal to PLC input EXI solid-state input relays MIS Ex-approved input sockets EXI24CH + MIS1CCNEX ATEX, IECEx and cULus HazLoc when assembled and installed as documented.
PLC output to field load EXO solid-state output relays MOS Ex-approved output sockets EXO24CHX + MOS1CCNEX ATEX, IECEx and cULus HazLoc when assembled and installed as documented.
High-voltage inductive DC load EXO CHA4 output relays MOS Ex-approved output sockets EXO24CHA4 + MOS1CCNEX Use only within the model-specific load, ambient and installation limits.

Published certificate references in the linked Delcon datasheets: DEMKO 13 ATEX 1041005U, IECEx ULD 13.0006U and cULus HazLoc file E332493.

Do not mix standard and Ex parts. A standard socket that is mechanically compatible is not automatically part of the certified assembly. Use only socket models explicitly named in the selected relay’s current documentation.

Where the interface fits

Typical Zone 2 relay-interface applications

Process skids and packages

Interface PLC I/O with valves, contactors, alarms and field signals in gas-classified package units, subject to the complete equipment design.

Pumps and compressors

Provide galvanic isolation and solid-state switching for auxiliary controls, status signals and actuator circuits in documented Zone 2 installations.

Marine and offshore systems

Use certified relay-and-socket combinations in suitable enclosures where the installation classification and applicable marine requirements are separately addressed.

Safety functions require separate assessment. An Ex-approved interface relay is not automatically a safety relay, SIL subsystem or emergency-shutdown function. Functional safety and explosion protection must both be engineered for the complete loop.

Selection workflow

Review the hazardous-area interface in five steps

1

Classify

Confirm zone, gas group, temperature conditions and the applicable regulatory scheme.

2

Define

Record control signal, load voltage, current, inrush, inductance and switching frequency.

3

Match

Select EXI + MIS for inputs or EXO + MOS for outputs using the exact documented models.

4

Install

Apply enclosure, wiring, spacing, fusing, temperature and socket-retention instructions.

5

Verify

Review the current certificate, datasheet, marking and complete equipment conformity file.

Engineering checklist

Information Delcon needs to review your application

✓

Area classification: zone, gas group and required equipment protection level.

✓

Ambient conditions: minimum/maximum temperature and heat inside the enclosure.

✓

PLC side: input/output voltage, available current, diagnostics and leakage.

✓

Field side: voltage, current, inrush, power factor or L/R and suppression.

✓

Mechanical installation: enclosure, DIN rail, spacing, socket and captive screw.

✓

Documentation: exact model revision, certificate, datasheet and equipment file.

Frequently asked questions

ATEX and IECEx relay basics

Can a Delcon Ex relay be used in Zone 1?

No. The published marking II 3G / Gc is intended for Zone 2 gas applications under the documented conditions. It does not cover Zone 0 or Zone 1.

Can I install an EXO relay in a standard Delcon socket?

Not as an Ex-approved assembly unless that exact socket is explicitly included in the current relay documentation. Use the specified Ex-approved MOS socket for EXO output relays and MIS socket for EXI input relays.

Does ATEX approval mean the relay is intrinsically safe?

No. The published protection concept is Ex nA / non-sparking, not Ex i intrinsic safety. If an intrinsically safe circuit is required, the complete loop needs a suitable Ex i design and assessment.

Do ATEX and IECEx certify the complete control cabinet?

No. They document conformity for the certified component and conditions stated in the certificate. The manufacturer of the complete equipment remains responsible for enclosure, wiring, temperature, other components and final conformity assessment.

Why does the certificate number end in “U”?

The “U” suffix identifies an Ex component certificate. The component is intended to be incorporated into complete equipment and used according to its conditions of certification.

Which documents should be included in the design file?

Keep the current relay and socket datasheets, certificates, markings, electrical calculations, temperature assessment, wiring diagram, component list and the complete equipment conformity assessment.

✓ Certification-safe wording based on current published Delcon product data · Reviewed 31 October 2026

Primary references

Verify the exact product before release

Send us the area classification and electrical load data.

Delcon can help identify the correct EXI/EXO relay and MIS/MOS socket combination for technical review.