How to Connect a 120/230 VAC Signal to a 24 VDC PLC Input

  • 10-year warranty
  • Pulse transformer technology
  • Made in Finland
  • cULus · CE · ATEX · HazLoc
Wiring concept for interfacing a 120 or 230 VAC field signal to a 24 VDC PLC input with a Delcon SLI input relay

A 120 VAC or 230 VAC field signal must never be wired directly to a 24 VDC PLC input. The practical solution is an input relay whose field side matches the AC signal and whose isolated solid-state output switches the PLC’s 24 VDC input circuit.

The design rule: select the relay input from the field voltage and device type, then wire the relay output as part of the PLC’s 24 VDC input loop. The relay becomes the galvanic boundary between the AC field circuit and the controller.

Why direct connection is not possible

A standard 24 VDC PLC input is designed around a defined DC voltage range, polarity, current threshold and common connection. Applying 120 VAC or 230 VAC to that input can destroy the input card and create a dangerous fault. A voltage divider or improvised resistor network is not an equivalent interface: it does not provide the required isolation, predictable switching thresholds or industrial noise immunity.

A purpose-designed input relay accepts the high-voltage AC signal on terminals A1 and A2. On the controller side, a separate normally open solid-state output closes the 24 VDC PLC input loop. The two circuits are galvanically isolated.

The diagram above shows a typical 24 VDC PLC input with its common at 0 V. Always verify the actual PLC input architecture, terminal designations and current requirement.

The signal chain, step by step

  1. The field device produces the AC signal. This may be a dry contact switching 120/230 VAC or a two-wire AC proximity sensor.
  2. The SLI relay detects the AC signal. Select a 120 VAC or 230/240 VAC input version to match the real field circuit.
  3. Pulse-transformer isolation separates field and control. The published input-output test voltage for these relay families is 4,600 VAC RMS for one second.
  4. The relay output switches the 24 VDC PLC loop. In a typical input-common-at-0-V circuit, +24 VDC is connected through the relay’s polarity-sensitive output to the PLC input channel.
  5. The PLC sees a clean DC state. The PLC no longer has to interpret the high-voltage field waveform, sensor leakage or capacitive current directly.
Electrical safety: 120/230 VAC wiring is hazardous. Installation, protective devices, segregation, earthing, conductor sizing and verification must be carried out by qualified personnel in accordance with the applicable electrical rules and the equipment manufacturers’ instructions. Isolate and prove dead before wiring.

Choose the relay from both voltage and field-device type

Field signal Recommended starting point Why
120 VAC from a dry contact or device with low off-state current SLI120CR Standard normally open AC-input relay for transferring a 120 VAC field state to a low-current DC PLC input circuit.
120 VAC from a two-wire proximity sensor SLI120CRP CRP variant intended for two-wire sensors that pass leakage current in their OFF state.
230/240 VAC from a dry contact or device with low off-state current SLI230CR Standard normally open AC-input relay for 230/240 VAC field signals.
230/240 VAC from a two-wire proximity sensor SLI230CRP CRP variant with a published 3.5 mA switch-off-current threshold for leakage-current applications.

The table is a selection starting point, not a substitute for the individual datasheet. Confirm maximum input voltage, switch-on and switch-off thresholds, field-device leakage current, cable capacitance, ambient temperature and installation method.

Standard CR or leakage-tolerant CRP?

Use a CR version when OFF really means OFF

A dry mechanical contact normally provides a clear open circuit. A conventional AC output with sufficiently low off-state current can also suit the standard CR input, provided its residual voltage and current remain below the relay’s switch-off region under worst-case conditions.

Use a CRP version for two-wire sensors

A two-wire AC sensor powers its electronics through the same pair used for signalling. It therefore passes some current even while OFF. CRP variants are designed to remain off in the presence of this leakage; the published switch-off-current figure is 3.5 mA.

Long parallel cable runs also create capacitance. With AC signals, that capacitance can pass current into an otherwise open input circuit. The result can be a relay that stays energised, flickers or changes state at an unexpected voltage. Use the real cable type and length when estimating the off-state current, and validate the complete loop—especially where a two-wire sensor and a long cable are combined.

Wire the 24 VDC output as an electronic contact

The relay output is a solid-state DC switching element, not a voltage source and not a potential-free mechanical contact. Published values for the SLI230CR and SLI230CRP include a 0–60 VDC load-voltage range, up to 50 mA load current, no minimum load requirement, approximately 0.2 V on-state voltage drop and 1 µA leakage current.

Observe the output polarity shown in the datasheet: terminal 13 is positive and terminal 14 negative. For a typical PNP-style 24 VDC PLC input with the input common at 0 V, connect +24 VDC to terminal 13, terminal 14 to the PLC input channel and the PLC input common to 0 V. If the input card uses another architecture, design the circuit from that card’s manual rather than copying the example.

Input-current check: confirm that the PLC channel’s ON-state current is below the relay’s permitted output current and above the PLC’s own ON threshold. Also check the PLC input’s off-state threshold against the relay’s published leakage current. The relay output should be used for PLC inputs and similar low-current DC loads; it is not a substitute for a power output relay.

120 VAC and 230 VAC applications differ at the field side

The 24 VDC PLC-side principle is the same for both voltage classes. The important differences are on the field side: relay model, maximum input voltage, switching thresholds, power consumption and the amount of current that cable capacitance or a sensor can pass while OFF.

Check 120 VAC circuit 230/240 VAC circuit
Relay family SLI120CR / SLI120CRP SLI230CR / SLI230CRP
Field overvoltage Verify the 120 V circuit maximum against the selected datasheet. SLI230CR/CRP datasheets publish a 265 VAC maximum input.
Two-wire sensor Use the sensor’s maximum leakage current and the 120 V cable calculation. Use the sensor’s maximum leakage current and the 230 V cable calculation; SLI230CRP publishes 3.5 mA switch-off current and 80 nF cable capacitance.
Protection and segregation Apply the requirements for the actual field voltage. Keep the AC field wiring segregated from the SELV/PELV control circuit as required by the installation design.

Common design mistakes

  • Connecting the AC signal directly to the PLC input. A 24 VDC input card is not an AC interface.
  • Selecting by nominal voltage only. The field device’s off-state leakage and cable capacitance can determine whether CR or CRP is correct.
  • Treating the solid-state output as a dry contact. Its polarity, voltage drop, leakage current, voltage range and current limit all matter.
  • Ignoring the PLC input manual. Common polarity, ON/OFF thresholds and channel test current vary by input card.
  • Testing only on the workbench. Validate the worst-case supply, longest cable, maximum temperature and real sensor.
  • Using one interface as a safety function. A standard input relay transfers a signal; it does not by itself create a safety-rated architecture.

Commissioning checklist

  • Record the actual field voltage at minimum, nominal and maximum supply conditions.
  • Obtain the device’s maximum OFF-state leakage current and minimum ON-state current.
  • Record cable type, length, routing and estimated capacitance.
  • Confirm relay switch-on/switch-off limits from the current datasheet.
  • Verify terminals A1/A2 and output polarity 13+/14− before energising.
  • Confirm PLC input common, ON/OFF thresholds and input current.
  • Test field OFF, field ON, wire break and loss-of-supply states.
  • Repeat the state test at the expected temperature and with adjacent channels energised as applicable.

Frequently asked questions

Can I use an ordinary interposing mechanical relay?

It can provide voltage conversion and isolation, but it introduces a coil, moving contacts, contact wear and potentially less predictable behaviour with leakage-current sensors. Compare the complete switching thresholds, lifetime, maintenance requirement and fault behaviour.

Why can a two-wire sensor keep a relay energised when it is supposedly off?

The sensor must power its electronics, so it passes a small off-state current. Cable capacitance adds another AC current path. If their combined current remains above the relay’s switch-off region, the interface may not release reliably.

Can the 50 mA output operate a solenoid?

No general assumption should be made. These SLI outputs are intended for PLC inputs and similar low-current DC loads. Select a dedicated output relay for a solenoid, contactor or other power load.

Does galvanic isolation remove the need for circuit protection?

No. Isolation separates the signal domains, but each circuit still requires the correct overcurrent protection, wiring method, segregation, earthing and safe installation.

Can the same output wiring be used with every PLC input card?

No. The example assumes an input common at 0 V. Check whether the actual input card is designed for a sourcing/PNP or sinking/NPN field device and follow its wiring diagram.

Review the complete signal loop before choosing the relay

Send Delcon the field voltage, device type, maximum leakage current, cable length and capacitance, PLC input-card model and ambient conditions. We can help identify the appropriate 120 VAC or 230 VAC input-relay variant for application testing.