Electromagnetic brake coils are compact actuators, but electrically they are demanding inductive loads. The combination of a Delcon SLO24CRA5 solid-state relay and a MIOS 1HI mounting socket creates a compact DIN-rail interface for controlling suitable DC brake coils from a 24 VDC PLC or control signal.
Why electromagnetic brakes are demanding loads
A brake coil stores energy in its magnetic field while energised. When current is interrupted, that stored energy produces a reverse-voltage transient. If the switching device and suppression arrangement are not selected together, repeated transients can overstress the output stage, disturb nearby control circuits or produce unpredictable release behaviour.
The solution is not simply to choose a relay by steady-state current. Coil voltage, operating current, inductance or L/R time constant, switching rate, ambient temperature and the required brake release time all influence the final selection.
How the SLO24CRA5 and MIOS 1HI work together
SLO24CRA5
A 24 VDC-controlled, normally open solid-state relay for DC loads. Its published load range is 0–380 VDC and 0–5 A, with no minimum load requirement.
It uses a pulse transformer for control-to-load isolation and specifies a 4,600 VAC RMS / 1 s input-output test voltage.
MIOS 1HI
A DIN-rail mounting socket for Delcon SL-series relays, designed to protect the relay against surge peaks produced by highly inductive devices.
Its published field-side nominal rating is up to 240 VDC / 170 VAC and its contact-current rating is 8 A RMS.
Compact DIN-rail control without mechanical contact wear
The SLO24CRA5 plugs directly into the MIOS 1HI socket. The socket mounts on a standard 35 mm DIN rail and provides screw terminals for the control and field wiring. Because the suppression function is incorporated in the mounting socket, the cabinet designer does not need to allocate a separate DIN-rail component solely for brake-coil surge suppression.
The solid-state switching stage also avoids contact bounce, arcing and mechanical contact wear. This is particularly useful where a brake is switched frequently or where long service intervals are important. The relay remains replaceable: if service is required, the plug-in relay can be changed without replacing the complete field wiring.
Published electrical limits
| Characteristic | SLO24CRA5 / MIOS 1HI information | Engineering significance |
|---|---|---|
| Control input | SLO24CRA5: nominal 24 VDC; 16 VDC switch-on and 14 VDC switch-off | Verify the controller output under real wiring and load conditions. |
| DC load current | SLO24CRA5: 0–5 A continuous; 20 A / 10 ms inrush | Check steady coil current and any energisation transient. |
| Inductive-load limit | SLO24CRA5: maximum L/R 50 ms at 24 V / 5 A | Obtain the brake-coil inductance or L/R value; current alone is not sufficient. |
| Switching time | SLO24CRA5: 0.3 ms typical switch-on and switch-off | The electrical relay is fast, but the suppression arrangement and brake mechanics determine the complete release response. |
| Socket field voltage | MIOS 1HI: nominal up to 240 VDC / 170 VAC | This socket rating limits the complete assembly even when the relay itself has a higher voltage rating. |
| Temperature | SLO24CRA5: −40…+70 °C; MIOS 1HI: −25…+70 °C | The complete combination is limited to the overlapping −25…+70 °C range, subject to relay derating and installation conditions. |
Endurance test with a highly inductive brake load
In one customer-specific endurance test, a Delcon MIOS 1HI-based relay solution switched an electromagnetic brake test load with an inductance of approximately 4.2 H. The setup ran continuously for 33 days and completed roughly four million switching cycles. The relay and socket remained operational, and no critical failures were observed during the test.
This result describes one defined test setup. It does not replace application-specific validation. Brake-coil voltage, current, inductance, duty cycle, release-time requirement, wiring and ambient conditions must be reviewed for each installation.
Information needed to select and validate the combination
- Control voltage: actual PLC or controller output voltage and available current.
- Brake-coil voltage and current: nominal values plus tolerances.
- Inductance or L/R: preferably from the brake manufacturer or a measured value.
- Switching duty: operations per minute or hour, on-time and expected lifetime cycles.
- Required release behaviour: the suppression method can influence the current-decay and mechanical release time.
- Installation conditions: ambient temperature, grouping, DIN-rail orientation, wiring length and available cabinet space.
- System safety: required performance level, redundancy, diagnostics and safe-state behaviour of the complete machine.
Where the combination can be useful
The solution is relevant wherever a controller must switch a suitable DC electromagnetic brake coil reliably in limited cabinet space. Potential applications include industrial vehicles, material-handling systems, hoists, conveyors, lifting equipment and other machines using spring-applied or electrically released brakes.
Compatibility must be confirmed from the actual brake data. In particular, applications with unusual release-time requirements, very high stored energy or safety-related stopping functions require joint review by the brake manufacturer, machine designer and relay supplier.
Frequently asked questions
Why use MIOS 1HI instead of an ordinary relay socket?
MIOS 1HI incorporates field-side surge suppression intended for highly inductive devices. This places the protective function close to the plug-in relay and reduces the need for a separate suppression module and additional cabinet wiring.
Can every 24 VDC brake coil be controlled with this combination?
No. The coil current, inductance or L/R, switching duty, required release time, ambient temperature and safety architecture must all fit the published limits and the complete application.
Does the combination eliminate all voltage transients?
No practical switching circuit eliminates stored energy. MIOS 1HI provides a defined suppression arrangement intended to control the transient and protect the relay. The complete behaviour still depends on the coil, wiring and operating conditions.
Does suppression affect brake release time?
It can. Suppression changes how quickly coil current decays after switch-off. Where release time is critical, it must be measured and validated with the actual brake and wiring.
Is SLO24CRA5 a safety relay?
No. It is a solid-state interface relay. Safety-related brake control requires an appropriate system architecture, diagnostics and validation beyond a single switching component.
Review the real brake-coil data with Delcon
Send us the coil voltage, current, inductance or L/R, switching frequency, required release time and ambient conditions. Delcon can review whether SLO24CRA5 with MIOS 1HI is an appropriate starting point for testing.