A relay interface does not have to mean hundreds of individually terminated wires. Delcon PLC Fast Connect™ combines plug-in input or output relays, an 8- or 16-position mounting base and a cable or system adapter selected for the PLC, DCS or remote-I/O card.
What PLC Fast Connect changes in the cabinet
Traditional point-to-point wiring is flexible, but repetitive. Every channel has to be identified, cut, stripped, terminated and checked separately. A pre-engineered relay interface moves much of that work into a defined cable and connector arrangement while retaining replaceable plug-in relays at the field interface.
The result is a cleaner boundary between the PLC or DCS and field wiring. The relay base remains on the DIN rail, individual relays can be replaced without rewiring the complete assembly, and the control-system connection can be reproduced consistently across several cabinets.
Three connection methods
1. Colour-coded flying leads for universal wiring
RC10X-xxx and RC20X-xxx cables have a 10- or 20-pole connector at the relay-base end and colour-coded individual conductors with ferrules at the other end. They are the flexible choice when the PLC or DCS uses ordinary terminal connections or when no dedicated adapter is required.
The xxx identifies cable length in centimetres. Standard lengths are selected in 50 cm increments, allowing the cable to be matched to the cabinet layout without leaving an unnecessary coil of spare wiring.
2. RC10 or RC20 cable with a system adapter
Where Delcon has a documented adapter for the I/O system, an RC10-xxx or RC20-xxx cable connects the MBS relay base to that adapter. The adapter provides the system-specific connector and pinout, so installation is based on a defined combination instead of terminal-by-terminal interpretation.
3. A direct preassembled cable
Some systems support a direct cable between the relay base and the control-system front connector. One documented example is the RC10-xxx S7-1500 solution for Siemens SIMATIC S7-1500. This removes the separate adapter from the signal path and creates a compact ready-made connection.
Choose 8 or 16 relay positions
| Base family | Channels | Terminal options | Typical reason to choose it |
|---|---|---|---|
| MBS8BIOP / MBS8BIOPCC | 8 | Screw / spring | A small I/O group, an eight-channel card section or a cabinet where channels are divided by machine function. |
| MBS16BIOP / MBS16BIOPCC | 16 | Screw / spring | A complete 16-channel I/O group with fewer bases and connector points. |
The base does not determine the electrical function by itself. Select compatible Delcon SL-series input or output relays for the actual signal, load voltage and load type. The MBS16BIOP, for example, supports PNP logic, 5–32 VDC on the logic side and nominal field-side voltages up to 250 VAC/DC; the selected relay still defines the channel’s switching behaviour and limits.
Documented PLC and remote-I/O options
| System | Delcon connection option | Documented I/O hardware |
|---|---|---|
| Siemens SIMATIC S7-300 | S7IO32L / S7IO32R or S300IO16 adapter | 16- and 32-channel S7-300 input/output arrangements using the specified Siemens front connector |
| Siemens SIMATIC S7-400 | S400IO32 adapter | 32-channel S7-400 I/O arrangement |
| Siemens SIMATIC S7-1500 | RC10-xxx S7-1500 direct cable | Direct connection to the specified Siemens front connector |
| Siemens ET 200SP HA | SET200 SP HA adapter | Adapter mounted in the specified push-in terminal block |
| Mitsubishi MELSEC Q | M82IO or M82IO2.5 adapter | QX81 input and QY81P output modules |
| ABB S800 / TU810 | TU810IO16 adapter | TU810 with DI810 input or DO810 output |
| ABB S800 / TU812 | RCTU812-xxx cable adapter | TU812 with DI810 input or DO810P output |
The table is a compatibility summary, not a substitute for checking the exact PLC or I/O-card code, connector, pinout and relay function. Product generations and I/O variants can use different front connectors even within the same control-system family.
What information is needed for selection?
- PLC, DCS or remote-I/O manufacturer and exact I/O-module code
- Input or output function, PNP or NPN logic and logic voltage
- Field signal or load voltage, current and load type for each channel
- Required channel count: 8, 16 or a combination of bases
- Screw or spring terminal preference on the field side
- Cable length, connector orientation and cabinet routing constraints
This information is enough to distinguish a universal flying-lead solution from a standard adapter combination or a direct cable.
Custom cables and adapters for other systems
A published adapter list cannot cover every PLC, DCS and remote-I/O platform—or every connector generation used in installed plants. If no standard Delcon option matches the hardware, Delcon can design and manufacture a custom cable, adapter or complete interface for the required connector, pinout, channel arrangement and cable length.
The custom design still starts with verified interface data. Providing the I/O-module code, connector specification and electrical function at the beginning avoids assumptions and makes the finished assembly repeatable for future cabinets and spare-part orders.
A practical selection sequence
- Select the relay: match the PLC signal or field load using Delcon’s input- or output-relay data.
- Select the base: choose 8 or 16 positions, logic type and screw or spring terminals.
- Select the connection: use RC10X/RC20X flying leads, an RC10/RC20 adapter combination or a documented direct cable.
- Verify the complete assembly: confirm module code, pinout, channel mapping, cable length and field-side electrical limits.
Want Delcon to define the complete interface?
Send us the I/O-module code, channel function, field-side data and preferred cable length. We can recommend the relays, MBS base and connection method—or design a custom cable or adapter when a standard combination is not available.