Relay Thermal Management for Continuous Duty: Load Current, Ambient Temperature and Installation Spacing

  • 10-year warranty
  • Pulse transformer technology
  • Made in Finland
  • cULus · CE · ATEX · HazLoc
Four checks for Delcon relay thermal management: model, ambient curve, grouped mounting and installation

For a relay that remains energized continuously, nameplate current alone does not define the permitted thermal operating point. Ambient temperature at the relay, adjacent continuously energized channels, spacing and DIN-rail orientation must be checked as separate inputs. The temperature-curve, grouped-bank and spacing rules in this guide are continuous-duty rules.

Scope: continuous duty. Apply the temperature-curve, grouped-bank and spacing rules below when the relay remains energized continuously. Start with the continuous current published for the exact product, then apply the model-specific conditions. Intermittent or frequently switched operation must be evaluated separately from its actual duty cycle and average current; peak, surge and all other electrical limits always apply.

Why current alone is not enough

The output stage and input circuit dissipate heat while the relay is energized. In continuous-duty operation this heat is present without an off period for cooling. As the air around the relay becomes warmer, less temperature headroom remains. Closely grouped, continuously energized relays also heat the same local air, so the relevant ambient is the temperature immediately around the relays where cooling airflow reaches them.

The current Delcon datasheets cited below provide an explicit continuous-duty load-versus-temperature curve and separate rules for continuously energized relays in grouped mounting. These rules are product-specific and must not be transferred to another model or used as blanket limits for intermittent operation.

Four checks for Delcon relay thermal management: model, ambient curve, grouped mounting and installation
For continuously energized relays, use four separate checks. A passed nameplate-current check does not override ambient, grouping, spacing or mounting limits.

1. Apply the model-specific curve for continuous duty

For the cited SLO24CR, SLO24CRA5 and SLO24TR datasheets, the allowed continuous load for a relay that remains energized is reduced linearly from 100% at +30 °C to one third at +70 °C. This is a model-specific continuous-duty curve, not a universal rule for every relay or duty cycle.

Ambient at the relays Share of published continuous-duty current SLO24CR / SLO24TR, 3 A rating SLO24CRA5, 5 A rating
+30 °C 100% 3.0 A 5.0 A
+40 °C 83⅓% 2.5 A 4.17 A
+50 °C 66⅔% 2.0 A 3.33 A
+60 °C 50% 1.5 A 2.5 A
+70 °C 33⅓% 1.0 A 1.67 A

Continuous-duty calculated values: the intermediate rows are linear interpolations from the datasheet endpoints for a relay that remains energized continuously. Round down when a practical design value is required and validate the complete application.

2. Treat a continuously energized relay bank as a thermal system

For these cited products, relays mounted together as a bank and remaining energized continuously have an additional limit: the total current of the continuously energized bank should be restricted to 50% of the capacity obtained from the temperature curve. Do not apply this 50% figure automatically to intermittent operation; assess the actual on/off pattern, duty cycle and average current instead.

This is a bank total, not permission for one channel to exceed its individual temperature-adjusted limit.

Continuous-duty example: eight SLO24CR relays at +50 °C

Assume that all eight adjacent SLO24CR relays remain energized continuously. The SLO24CR is rated at 3 A, and at +50 °C the cited continuous-duty curve gives 2 A per relay. The bank therefore has 16 A of summed curve capacity. Applying the 50% continuous-bank rule gives an 8 A total-current budget. This can mean eight equally loaded channels at 1 A each. If some channels switch intermittently, evaluate that operating sequence separately rather than treating this continuous-duty example as a blanket limit.

3. Understand what the 12.5 mm spacing changes

Continuously energized relays grouped together

Apply both the product-specific continuous-duty temperature curve and the additional 50% bank total-current restriction.

At least 12.5 mm between continuously energized relays

The cited datasheets say the additional continuous-bank restriction does not apply. The individual continuous-duty temperature curve and all other electrical limits still apply.

For continuous duty, spacing is a design lever rather than an exemption from thermal validation. If panel width is scarce, reduce the continuously energized current or divide the relay population into thermally separated groups. Evaluate intermittent sequences separately from their actual duty cycle.

4. Verify rail orientation and switching duty

For the continuous-duty thermal checks in this guide, the cited datasheets strongly recommend installing relays with compatible MOS1-series sockets and MBS8/MBS16 mounting bases on a horizontal DIN rail to support proper cooling. If the rail is vertical, the continuously energized installation must be checked to ensure the relays do not become too hot.

Intermittent and frequently switched applications are a separate case. Evaluate their actual duty cycle and average current over a representative period. Current, inrush, switching frequency and surge limits remain separate checks even when the relay is not continuously energized.

Cabinet design checklist

  • Identify the exact relay and use its current Delcon datasheet.
  • Determine whether the relay remains energized continuously; apply the curve, bank and spacing rules below only to that continuous-duty state.
  • Measure or estimate the worst-case ambient immediately around the continuously energized relay bank.
  • Apply the model-specific load-versus-temperature curve to continuous-duty operation.
  • Count continuously energized adjacent channels and calculate the continuous-duty bank total.
  • Decide whether at least 12.5 mm spacing is available where the datasheet permits that exception.
  • Prefer the datasheet-recommended horizontal DIN-rail orientation.
  • Check continuous current, inrush, load type, L/R or suppression, switching frequency and fuse selection separately.
  • Validate the worst continuous-duty operating state after the cabinet reaches thermal equilibrium.
Selection boundary: the temperature-curve, grouped-bank and spacing rules in this guide are for continuously energized operation of the cited Delcon examples. Intermittent duty, enclosure ventilation, neighbouring heat sources, wiring, socket choice, load waveform and safety architecture require application-specific evaluation.

Frequently asked questions

Does a 3 A relay always carry 3 A continuously?

No. For a relay that remains energized continuously, 3 A is only the starting rating. The selected model-specific temperature curve, grouped-bank rule and installation conditions may reduce the permitted continuous-duty operating point.

Does 12.5 mm spacing remove all continuous-duty derating?

No. For continuously energized relays in the cited datasheets, it removes only the additional grouped-bank restriction. The individual continuous-duty temperature curve and every electrical limit still apply.

Do these limits apply automatically to intermittent operation?

No. The curve, 50% bank rule and 12.5 mm spacing exception described here are continuous-duty conditions. Evaluate intermittent operation from the actual on/off sequence, duty cycle and average current, while respecting peak and surge limits.

Can I use enclosure temperature as the ambient value?

Use the worst-case temperature in the immediate vicinity of the relays, where airflow reaches them. A remote enclosure sensor can miss a local hot spot.

Is vertical DIN-rail mounting forbidden?

The cited datasheets recommend horizontal installation for proper cooling. With vertical rail orientation, the design must ensure that the relays do not become too hot.

For the wider electrical selection sequence, see How to Select a Solid-State Output Relay for the Actual Load.

Ask Delcon to review the thermal operating point

Send the relay model, load voltage and current profile, whether the relay remains continuously energized, actual duty cycle, inrush or L/R data, switching frequency, number of adjacent energized channels, spacing, DIN-rail orientation and worst-case ambient temperature at the relay bank.