How to Select a Solid-State Output Relay for the Actual Load

  • 10-year warranty
  • Pulse transformer technology
  • Made in Finland
  • cULus · CE · ATEX · HazLoc
Flowchart for selecting an AC TRIAC or DC MOSFET solid-state output relay from the actual load

Selecting a solid-state output relay starts with the load, not with a generic “amps” figure. The correct relay must match the control voltage, AC or DC load circuit, working voltage, continuous current, inrush current and—in an inductive DC application—the load’s L/R time constant.

Delcon rating principle: use the continuous load-current value published for the selected Delcon product. No additional arbitrary derating factor is required. The other published limits—load voltage, inrush, load type, L/R, protection and installation conditions—still have to match the application.

1. Start with the control signal

The relay input must match the PLC or controller output. The products in the examples below use either a 24 VDC or 48 VDC control signal. Check the guaranteed switch-on and switch-off thresholds as well as the nominal voltage; this confirms the controller can both energise and release the relay reliably.

2. Separate AC and DC loads immediately

An AC triac output and a DC MOSFET output are not interchangeable.

  • AC load: use a relay designed for AC switching, such as the SLO24TR. Its triac output is specified for 0–265 VAC.
  • DC load: use a MOSFET output such as SLO24CR, SLO48CRA5 or the integrated SLO24CRXSN.

The load voltage must remain inside the complete specified range in normal operation and during transients. Do not select a relay only because its nominal voltage resembles the system voltage.

3. Use the published continuous-current rating directly

For Delcon products, the stated continuous load current is the usable continuous rating for the product under its specified operating and installation conditions. There is no need to invent an extra safety percentage or reduce the number with a generic rule taken from another manufacturer.

Do not confuse continuous current with inrush current. The inrush figure is a short-duration capability, not a higher continuous rating. Equally, a load whose steady current is below the relay rating can still be unsuitable if its starting pulse exceeds the published inrush limit.

4. Check inrush from the load manufacturer’s data

Solenoid valves, contactor coils, lamps, capacitive inputs and DC motors may draw substantially more current at switching than during steady operation. Obtain the maximum inrush amplitude and duration from the load manufacturer, then compare both values with the relay specification.

For example, the SLO24TR is rated at 3 A continuous and 90 A for 20 ms inrush. The SLO24CR is rated at 3 A continuous and 15 A for 10 ms inrush. These values describe different switching technologies and cannot be exchanged between AC and DC applications.

5. For DC coils, verify L/R and suppression

The L/R time constant describes how quickly current in an inductive DC load changes. A longer time constant means more stored magnetic energy and a more demanding turn-off event. Compare the actual coil data with the relay’s model-specific L/R condition.

A clamp diode is required where the selected relay datasheet calls for one. The diode limits the turn-off voltage but also slows current decay, which can lengthen the mechanical release time of a valve or contactor. If release time matters, evaluate the complete suppression method rather than changing components by habit.

6. Confirm leakage, voltage drop and minimum load

A solid-state output is not an ideal dry contact. It has a specified off-state leakage current and on-state voltage drop. Sensitive loads must remain off at the maximum leakage current and still receive enough voltage when the relay is on.

The four examples below specify no minimum load requirement, which is valuable for low-current interface circuits. The exact leakage and voltage-drop values remain model-specific and must be checked from the selected datasheet.

Delcon output-relay comparison

Model Output technology Load range Continuous / inrush Key load condition
SLO24TR Triac, AC 0–265 VAC 3 A / 90 A, 20 ms Check AC load inrush and switching frequency.
SLO24CR MOSFET, DC 0–66 VDC 3 A / 15 A, 10 ms L/R 5 ms at 24 V / 2 A.
SLO48CRA5 MOSFET, DC 0–380 VDC 5 A / 20 A, 10 ms L/R 50 ms at 24 V / 5 A; 48 VDC control.
SLO24CRXSN MOSFET, DC 0–32 VDC 10 A / 80 A, 10 ms Resistive or slightly inductive load; L/R limits are operating-point specific.

Values above are a selection summary, not a substitute for the current product datasheet.

Two worked selection examples

Example A: 230 VAC contactor coil controlled by a 24 VDC PLC output

The load is AC, so begin with a triac-output product such as SLO24TR. Confirm that the actual supply stays within 0–265 VAC, the coil’s pull-in current and duration stay within 90 A / 20 ms, and the 3 A continuous rating is sufficient. Then verify switching frequency, fuse selection and the contactor manufacturer’s coil data.

Example B: 24 VDC solenoid controlled by a 24 VDC PLC output

The load is DC, so use a MOSFET-output relay. Suppose the solenoid draws 1.6 A continuously and its manufacturer specifies L/R = 4 ms. SLO24CR is a possible starting point because its datasheet specifies 0–3 A and L/R 5 ms at 24 V / 2 A. Confirm the starting pulse, use the required clamp diode, check release-time requirements and size the fuse for the complete circuit.

Protection and installation checks

  • Use a correctly rated fast fuse where specified to limit short-circuit and overload damage.
  • Use the compatible socket and conductor size; SLO plug-in relays use output-relay bases such as MOS1GN.
  • Follow the selected datasheet for wiring, mounting, cooling and conductor requirements.
  • Verify the circuit at minimum and maximum supply voltage and under the real switching duty.
  • Do not use an ordinary interface relay as a safety-isolation device unless the complete certified safety function explicitly permits it.

A concise selection rule

Use the published Delcon continuous-current value as the continuous rating. Then make four separate pass/fail checks: AC or DC technology, load-voltage range, inrush capability and load-specific behaviour such as L/R and suppression. A relay is suitable only when every check passes.

Want Delcon to verify the load?

Send us the controller output data and the load manufacturer’s voltage, continuous current, inrush and inductive-load information. We can recommend the relay, socket and protection arrangement.

Contact Delcon Read the inductive-load protection guide