1. Leakage supplies the residual path
Two-wire electronic sensors normally pass a small current even when they are off because the same two conductors power the sensor electronics.
Engineering guide · PLC and DCS inputs
A field signal that stays on, releases slowly or flickers is usually an interface problem—not random PLC behaviour. Use the actual sensor leakage, total cable capacitance and guaranteed input thresholds to find the cause.
Two-wire electronic sensors normally pass a small current even when they are off because the same two conductors power the sensor electronics.
The longer the cable, the more capacitance the receiver sees. Parallel power wiring can add coupled disturbances.
A signal becomes unreliable when the resulting voltage sits near the PLC input’s guaranteed on/off thresholds.
Quick answer
The receiving input still sees enough current or voltage to stay above its switch-off threshold. Common contributors are sensor off-state leakage, cable capacitance, coupled interference, an overly sensitive input, or an unintended return path.
Cable capacitance
The cable manufacturer normally specifies capacitance per metre. Multiplying that figure by the installed length gives a useful first estimate of total cable capacitance.
Use the capacitance figure for the actual conductor arrangement in your circuit.
Cable geometry, shielding, parallel conductors, sensor electronics and the receiver input network all affect the real circuit. The calculation is a screening tool, not final design approval.
Field troubleshooting
Work from measured field conditions toward the receiver. This avoids replacing sensors or PLC cards without evidence.
Sensor model, supply, cable type and length, route, PLC card and channel configuration.
Voltage at the receiver in both states and during the switching event, using suitable instruments and safe procedures.
Check leakage, total capacitance and measured voltage against guaranteed on/off thresholds.
Test minimum and maximum supply voltage and real nearby switching conditions before release.
Focus first on off-state leakage, total cable capacitance and the switch-off threshold. Disconnecting or shortening the field cable for a controlled test can help separate the sensor from the installed cable effect.
Check separation from motor and contactor wiring, shield termination, grounding, surge suppression and the actual disturbance at the receiver. Do not treat shielding as a substitute for defined thresholds.
Delcon input relay selection
The field-side voltage determines the input relay. The relay then provides a separate solid-state DC output for the PLC or DCS input.
| Field signal | Starting point | Published thresholds | Key design check |
|---|---|---|---|
| 24 VDC | SLI24CR | 16 VDC on / 14 VDC off | Measure both states at the relay input; verify the required 0.3 ms response and the complete installation. |
| 120 VAC two-wire sensor | SLI120CRP | 80 VAC on / 60 VAC off | 3.5 mA switch-off current and 80 nF specified cable capacitance. |
| 230–240 VAC two-wire sensor | SLI230CRP | 160 VAC on / 140 VAC off | 3.5 mA switch-off current and 80 nF specified cable capacitance. |
The examples above share a 0–60 VDC, 0–50 mA solid-state output with no minimum load, 1 µA specified leakage and 0.2 V voltage drop. Always use the current product datasheet for final design, wiring, mounting and protection.
Design review
Sensor: manufacturer, exact type, AC/DC supply and maximum off-state leakage.
Cable: length, capacitance per metre, conductor arrangement, shielding and route.
Receiver: PLC/DCS model, I/O card, channel type and guaranteed input thresholds.
Measurements: voltage in both states and, when relevant, the switching waveform.
Environment: nearby contactors, motors, drives, solenoids and their suppression.
Timing: maximum permitted turn-on and release delay for the process.
Frequently asked questions
Usually not. Its internal electronics normally require a small off-state current. The sensor datasheet should state the maximum leakage or residual current.
No. A high-impedance meter can display capacitively coupled or residual voltage that cannot supply meaningful current. Measure and interpret the circuit with suitable instruments and the receiver characteristics in mind.
No. Shielding and routing can reduce coupled interference, but they do not remove sensor leakage or cable capacitance. The receiver still needs suitable thresholds and hysteresis.
Sometimes a correctly engineered load can change the off-state voltage, but it also changes current, dissipation, safety and fault behaviour. Do not add a component without calculating and approving the complete circuit.
Use one when the field signal needs defined on/off thresholds, galvanic isolation and a predictable low-leakage DC output for the PLC or DCS input. Select the model from the actual field voltage and signal type.