Engineering guide · PLC and DCS inputs

Long signal cables, leakage current and false PLC inputs

A field signal that stays on, releases slowly or flickers is usually an interface problem—not random PLC behaviour. Use the actual sensor leakage, total cable capacitance and guaranteed input thresholds to find the cause.

How a long sensor cable can create a false PLC input A two-wire field sensor has off-state leakage. A long cable adds capacitance and can collect interference. A Delcon input relay applies defined switching thresholds and galvanically isolates the PLC input. From uncertain field signal to defined PLC state Two-wire sensor Off-state leakage Long field cable Capacitance + coupled noise Residual voltage may remain PLC input Threshold? 0 or 1 Delcon input relay interface Defined switch-on / switch-off thresholds Pulse-transformer isolation · low-leakage DC output
The relay separates field-side signal evaluation from the controller-side input.

1. Leakage supplies the residual path

Two-wire electronic sensors normally pass a small current even when they are off because the same two conductors power the sensor electronics.

2. Cable capacitance stores and transfers charge

The longer the cable, the more capacitance the receiver sees. Parallel power wiring can add coupled disturbances.

3. The receiver decides the logic state

A signal becomes unreliable when the resulting voltage sits near the PLC input’s guaranteed on/off thresholds.

Quick answer

Why does a PLC input remain on after the sensor turns off?

The receiving input still sees enough current or voltage to stay above its switch-off threshold. Common contributors are sensor off-state leakage, cable capacitance, coupled interference, an overly sensitive input, or an unintended return path.

Typical symptoms

  • The input releases after a noticeable delay.
  • The channel flickers when motors, contactors or drives switch.
  • The fault appears only on the longest cable runs.
  • The input works on the bench but not in the installed cable route.
  • A multimeter shows voltage even when the sensor is off.

What a robust interface must provide

  • A guaranteed switch-on threshold.
  • A lower, separate switch-off threshold.
  • Enough hysteresis between the two states.
  • A known cable-capacitance limit where specified.
  • A predictable, isolated output for the PLC or DCS card.
Do not diagnose from nominal voltage alone. Record the voltage at the receiver with the sensor both on and off, then compare those values with guaranteed thresholds—not with a general “24 V” or “230 V” label.

Cable capacitance

Calculate the cable contribution before selecting the interface

The cable manufacturer normally specifies capacitance per metre. Multiplying that figure by the installed length gives a useful first estimate of total cable capacitance.

Total cable capacitanceCtotal = Cper metre × length

Use the capacitance figure for the actual conductor arrangement in your circuit.

Illustrative calculation—not a Delcon measurement

  1. Example cable capacitance: 100 pF/m
  2. Installed cable length: 500 m
  3. Total: 100 pF/m × 500 m = 50,000 pF = 50 nF
  4. Compare the result with the selected receiver’s published cable-capacitance limit and verify the complete circuit in real operating conditions.

Cable geometry, shielding, parallel conductors, sensor electronics and the receiver input network all affect the real circuit. The calculation is a screening tool, not final design approval.

Field troubleshooting

A practical diagnostic workflow

Work from measured field conditions toward the receiver. This avoids replacing sensors or PLC cards without evidence.

1

Document

Sensor model, supply, cable type and length, route, PLC card and channel configuration.

2

Measure

Voltage at the receiver in both states and during the switching event, using suitable instruments and safe procedures.

3

Compare

Check leakage, total capacitance and measured voltage against guaranteed on/off thresholds.

4

Verify

Test minimum and maximum supply voltage and real nearby switching conditions before release.

If the input releases slowly

Focus first on off-state leakage, total cable capacitance and the switch-off threshold. Disconnecting or shortening the field cable for a controlled test can help separate the sensor from the installed cable effect.

If the input flickers during other switching

Check separation from motor and contactor wiring, shield termination, grounding, surge suppression and the actual disturbance at the receiver. Do not treat shielding as a substitute for defined thresholds.

Delcon input relay selection

Match the relay to the field signal

The field-side voltage determines the input relay. The relay then provides a separate solid-state DC output for the PLC or DCS input.

Field signal Starting point Published thresholds Key design check
24 VDC SLI24CR 16 VDC on / 14 VDC off Measure both states at the relay input; verify the required 0.3 ms response and the complete installation.
120 VAC two-wire sensor SLI120CRP 80 VAC on / 60 VAC off 3.5 mA switch-off current and 80 nF specified cable capacitance.
230–240 VAC two-wire sensor SLI230CRP 160 VAC on / 140 VAC off 3.5 mA switch-off current and 80 nF specified cable capacitance.

The examples above share a 0–60 VDC, 0–50 mA solid-state output with no minimum load, 1 µA specified leakage and 0.2 V voltage drop. Always use the current product datasheet for final design, wiring, mounting and protection.

Design review

Information needed to resolve the problem

✓

Sensor: manufacturer, exact type, AC/DC supply and maximum off-state leakage.

✓

Cable: length, capacitance per metre, conductor arrangement, shielding and route.

✓

Receiver: PLC/DCS model, I/O card, channel type and guaranteed input thresholds.

✓

Measurements: voltage in both states and, when relevant, the switching waveform.

✓

Environment: nearby contactors, motors, drives, solenoids and their suppression.

✓

Timing: maximum permitted turn-on and release delay for the process.

Need multi-channel PLC connectivity? Delcon PLC Fast Connect™ combines 8- or 16-channel mounting bases with cables and system adapters. Delcon can also design a custom cable or adapter for another PLC, DCS or remote-I/O platform. See the PLC Fast Connect guide →

Frequently asked questions

Long-cable and false-input basics

Can a two-wire sensor be truly open when it is off?

Usually not. Its internal electronics normally require a small off-state current. The sensor datasheet should state the maximum leakage or residual current.

Does a voltage reading on an open cable prove a usable current is present?

No. A high-impedance meter can display capacitively coupled or residual voltage that cannot supply meaningful current. Measure and interpret the circuit with suitable instruments and the receiver characteristics in mind.

Is shielding enough to prevent false PLC inputs?

No. Shielding and routing can reduce coupled interference, but they do not remove sensor leakage or cable capacitance. The receiver still needs suitable thresholds and hysteresis.

Can I add a resistor to bleed away the residual voltage?

Sometimes a correctly engineered load can change the off-state voltage, but it also changes current, dissipation, safety and fault behaviour. Do not add a component without calculating and approving the complete circuit.

When should I use a Delcon input relay?

Use one when the field signal needs defined on/off thresholds, galvanic isolation and a predictable low-leakage DC output for the PLC or DCS input. Select the model from the actual field voltage and signal type.

✓ Source: current SLI24CR, SLI120CRP and SLI230CRP datasheets · Draft prepared for Delcon technical review · 11 October 2026

Send us the circuit data—not just the nominal voltage.

With the sensor datasheet, cable details, PLC input data and measurements, Delcon can help identify the cause and select the interface.

Discuss your application →