1. Define the direction
Field signal to controller input means an input relay. Controller output to field load means an output relay.
Engineering guide · Industrial I/O interfaces
Start with signal direction—not a familiar part number. Then verify field voltage, load behaviour, leakage or inrush, cable effects, isolation, mounting and thermal conditions before selecting the relay and connection system.
Field signal to controller input means an input relay. Controller output to field load means an output relay.
Nominal voltage is only the start. Use guaranteed thresholds, current, inrush, L/R, leakage and switching time.
Include socket or base, fuse and suppression, cable/adapter, ambient temperature, mounting and controller I/O behaviour.
Six-step workflow
A reliable choice follows the signal from source to destination and checks the complete circuit. The sequence below applies to new designs, retrofits and fault investigations.
Field device → PLC/DCS input, or PLC/DCS output → field load?
Record AC/DC, nominal range, tolerances, polarity and the controller-side voltage.
For inputs: thresholds, leakage and cable capacitance. For outputs: continuous current, inrush, L/R and switching rate.
Verify dielectric isolation, expected off-state leakage, voltage drop and required fail-safe behaviour.
Check ambient temperature, mounting direction, relay-bank loading, approvals and disturbance level.
Choose an individual MIS/MOS socket or an MBS8/MBS16 base with the correct PLC/DCS cable or adapter.
Selection map
This decision map narrows the product family. It does not replace application-specific verification.
Field signals to controller inputs
An input relay evaluates the field-side signal and provides an isolated solid-state DC output for the PLC or DCS input. Use the guaranteed switch-on and switch-off values when checking compatibility.
| Application starting point | Candidate | Verified field-side thresholds | Controller-side output | Main check |
|---|---|---|---|---|
| 24 VDC field signal | SLI24CR | 16 VDC on / 14 VDC off | 0–60 VDC, 0–50 mA; 1 µA leakage | Measure both states at the relay input and verify polarity and 0.3 ms switching time. |
| 230/240 VAC contact or conventional signal | SLI230CR | 160 VAC on / 120 VAC off | 0–60 VDC, 0–50 mA; 1 µA leakage | Verify off-state voltage, cable effects and the published 50 ms switching times. |
| 230/240 VAC two-wire proximity sensor | SLI230CRP | 160 VAC on / 140 VAC off; 3.5 mA switch-off current | 0–60 VDC, 0–50 mA; 1 µA leakage | Designed for two-wire proximity sensors; verify its specified 80 nF cable-capacitance limit. |
The P suffix is not a cosmetic variant. SLI230CRP has characteristics intended for two-wire proximity sensors, including a published switch-off current and cable-capacitance limit. Do not silently substitute it for SLI230CR or vice versa.
Record sensor off-state leakage, cable capacitance per metre and total length, then compare measured on/off voltage with the relay thresholds. See the long-cable diagnostic guide.
Controller outputs to field loads
An output relay protects the PLC or DCS output from the field circuit and switches the load. Continuous current alone is not enough: verify inrush, inductive time constant, operating frequency and thermal loading.
| Load starting point | Candidate | Verified load range | Transient / inductive capability | Main check |
|---|---|---|---|---|
| General low-voltage DC load | SLO24CR | 0–66 VDC, 0–3 A; no minimum load | 15 A / 10 ms inrush; L/R 5 ms at 24 V / 2 A | Verify actual coil L/R or inrush, suppression and required release time. |
| Demanding inductive DC load or higher DC voltage | SLO24CRA5 | 0–380 VDC, 0–5 A; no minimum load | 20 A / 10 ms inrush; L/R 50 ms at 24 V / 5 A | Check stored energy, switching frequency, external suppression and thermal derating. |
| AC load such as contactor, valve or lamp | SLO24TR | 0–265 VAC, 0–3 A; no minimum load | 90 A / 20 ms inrush; 4000 V/µs triac dV/dt | Verify load inrush and average current at the real switching duty. |
Sockets and multi-channel interfaces
The relay defines the electrical function. The socket or mounting base defines how the channel is installed, maintained and connected to the controller.
MIS1GN is the screw-terminal DIN-rail socket for SLI input relays. A spring-terminal MIS1CCN variant is also available.
MOS1GN is the screw-terminal DIN-rail socket for SLO output relays. A spring-terminal MOS1CCN variant is also available.
MBS8BIOP / MBS16BIOP bases accept input and output relays. Screw, spring and test-point variants support different cabinet and maintenance requirements.
RC10/RC20 cable families connect MBS bases using flying leads, a controller-specific adapter or, for supported systems, a direct front-connector cable. Confirm connector pinout, channel count, logic and cable length for the exact I/O card.
Current MBS16BIOP documentation specifies 5–32 VDC on the logic side, up to 250 VAC/DC on the field side, 8 A maximum continuous contact current and at least 4600 VAC rms I/O breakdown voltage. These base limits do not replace the selected relay’s own limits.
Thermal and protection review
Ambient and derating: use the relay’s temperature curve. Current output-relay datasheets derate permitted continuous load above +30 °C.
Relay bank: check the additional long-duration bank-loading rule and whether spacing changes it.
Mounting: follow the datasheet recommendation for horizontal DIN-rail installation and cooling.
Short circuit and overload: choose a fast fuse suited to both load and relay; verify its real protective coordination.
Off state: confirm leakage current and voltage drop are acceptable to the load or controller input.
Approvals: verify the exact relay-and-socket combination for UL, ATEX/IECEx or other project requirements.
Information for final selection
Controller: manufacturer, CPU/remote-I/O system, exact I/O card and PNP/NPN or sourcing/sinking logic.
Signal direction: field-to-input or output-to-load, plus required normal and fault state.
Voltage: AC/DC, nominal range, tolerances, polarity and frequency where applicable.
Device data: sensor leakage and cable capacitance, or load current, inrush and L/R.
Duty: switching frequency, on-time, release-time requirement and expected lifetime.
Installation: channel count, ambient temperature, mounting, terminal preference, approvals and cable route.
Frequently asked questions
An input relay receives a field-side signal and provides an isolated signal to a PLC or DCS input. An output relay receives the controller command and switches a field-side load. Reversing the direction changes both the electrical specification and the socket wiring.
No. Check load voltage, AC/DC type, inrush, inductive L/R, switching frequency, ambient temperature and protection. A coil or lamp can momentarily demand many times its steady current.
They have different input characteristics. SLI230CRP is intended for two-wire proximity sensors and publishes a switch-off current and cable-capacitance limit. Each suffix identifies a distinct model.
Use an MBS8 or MBS16 base when several channels benefit from dense mounting and a shared cable/adapter connection to the PLC or DCS. For a single or dispersed channel, an individual MIS or MOS socket may be simpler.
No. Isolation is only one design parameter. The interface must also meet voltage, current, threshold, timing, thermal, protection, wiring and approval requirements.