Engineering guide · Industrial I/O interfaces

How to select a PLC or DCS interface relay

Start with signal direction—not a familiar part number. Then verify field voltage, load behaviour, leakage or inrush, cable effects, isolation, mounting and thermal conditions before selecting the relay and connection system.

Input relay and output relay signal directionsA Delcon input relay receives a field signal and drives a controller input. A Delcon output relay receives a controller output and switches a field load. Choose the direction first Field signalsensor / contact Input relaySLI familydefined thresholds PLC / DCSinput card PLC / DCSoutput card Output relaySLO familyload switching Field loadcoil / valve / lamp
Input and output relays solve opposite interface problems.

1. Define the direction

Field signal to controller input means an input relay. Controller output to field load means an output relay.

2. Select from real electrical data

Nominal voltage is only the start. Use guaranteed thresholds, current, inrush, L/R, leakage and switching time.

3. Engineer the complete channel

Include socket or base, fuse and suppression, cable/adapter, ambient temperature, mounting and controller I/O behaviour.

Six-step workflow

Choose the interface in the right order

A reliable choice follows the signal from source to destination and checks the complete circuit. The sequence below applies to new designs, retrofits and fault investigations.

1

Signal direction

Field device → PLC/DCS input, or PLC/DCS output → field load?

2

Voltage and polarity

Record AC/DC, nominal range, tolerances, polarity and the controller-side voltage.

3

Source or load behaviour

For inputs: thresholds, leakage and cable capacitance. For outputs: continuous current, inrush, L/R and switching rate.

4

Isolation and faults

Verify dielectric isolation, expected off-state leakage, voltage drop and required fail-safe behaviour.

5

Environment

Check ambient temperature, mounting direction, relay-bank loading, approvals and disturbance level.

6

Connection system

Choose an individual MIS/MOS socket or an MBS8/MBS16 base with the correct PLC/DCS cable or adapter.

Selection rule: a matching nominal voltage does not prove compatibility. Final approval requires the current product datasheet plus the field-device, load and PLC/DCS card specifications.

Selection map

From signal direction to a Delcon starting point

This decision map narrows the product family. It does not replace application-specific verification.

PLC and DCS interface relay selection mapInput relays connect field signals to controller inputs. Output relays connect controller outputs to field loads. Both paths end with engineering checks and selection of a socket or multi-channel mounting base. PLC/DCS interface relay selection — start with signal direction What must cross the isolation boundary? Field signal → PLC/DCS inputSelect a Delcon input relay (SLI family)Verify AC/DC voltage, thresholds, leakage and cable capacitance PLC/DCS output → field loadSelect a Delcon output relay (SLO family)Verify AC/DC load, current, inrush, L/R and switching rate Input-relay starting points24 VDC: SLI24CR230/240 VAC: SLI230CR · 2-wire sensor: SLI230CRP Output-relay starting points24 VDC load: SLO24CR · demanding DC: SLO24CRA5AC load up to 265 VAC: SLO24TR Final engineering checksIsolation · fail-safe behaviour · fuse/protection · ambient temperature · deratingIndividual MIS/MOS socket or 8/16-channel MBS + cable/adapter

Field signals to controller inputs

Select an input relay from the actual field signal

An input relay evaluates the field-side signal and provides an isolated solid-state DC output for the PLC or DCS input. Use the guaranteed switch-on and switch-off values when checking compatibility.

Application starting point Candidate Verified field-side thresholds Controller-side output Main check
24 VDC field signal SLI24CR 16 VDC on / 14 VDC off 0–60 VDC, 0–50 mA; 1 µA leakage Measure both states at the relay input and verify polarity and 0.3 ms switching time.
230/240 VAC contact or conventional signal SLI230CR 160 VAC on / 120 VAC off 0–60 VDC, 0–50 mA; 1 µA leakage Verify off-state voltage, cable effects and the published 50 ms switching times.
230/240 VAC two-wire proximity sensor SLI230CRP 160 VAC on / 140 VAC off; 3.5 mA switch-off current 0–60 VDC, 0–50 mA; 1 µA leakage Designed for two-wire proximity sensors; verify its specified 80 nF cable-capacitance limit.

Choose the CRP variant deliberately

The P suffix is not a cosmetic variant. SLI230CRP has characteristics intended for two-wire proximity sensors, including a published switch-off current and cable-capacitance limit. Do not silently substitute it for SLI230CR or vice versa.

Long cable or false input?

Record sensor off-state leakage, cable capacitance per metre and total length, then compare measured on/off voltage with the relay thresholds. See the long-cable diagnostic guide.

Controller outputs to field loads

Select an output relay from the real load

An output relay protects the PLC or DCS output from the field circuit and switches the load. Continuous current alone is not enough: verify inrush, inductive time constant, operating frequency and thermal loading.

Load starting point Candidate Verified load range Transient / inductive capability Main check
General low-voltage DC load SLO24CR 0–66 VDC, 0–3 A; no minimum load 15 A / 10 ms inrush; L/R 5 ms at 24 V / 2 A Verify actual coil L/R or inrush, suppression and required release time.
Demanding inductive DC load or higher DC voltage SLO24CRA5 0–380 VDC, 0–5 A; no minimum load 20 A / 10 ms inrush; L/R 50 ms at 24 V / 5 A Check stored energy, switching frequency, external suppression and thermal derating.
AC load such as contactor, valve or lamp SLO24TR 0–265 VAC, 0–3 A; no minimum load 90 A / 20 ms inrush; 4000 V/µs triac dV/dt Verify load inrush and average current at the real switching duty.
For inductive loads: select from the coil’s measured or documented steady current, inrush, L/R time constant, switching frequency and release-time requirement. Suppression can reduce voltage stress but may slow release. See Switching Inductive DC Loads and Solenoid Valves Reliably.

Sockets and multi-channel interfaces

Choose the connection architecture after the relay

The relay defines the electrical function. The socket or mounting base defines how the channel is installed, maintained and connected to the controller.

Individual input channel

MIS1GN is the screw-terminal DIN-rail socket for SLI input relays. A spring-terminal MIS1CCN variant is also available.

Individual output channel

MOS1GN is the screw-terminal DIN-rail socket for SLO output relays. A spring-terminal MOS1CCN variant is also available.

8 or 16 channels

MBS8BIOP / MBS16BIOP bases accept input and output relays. Screw, spring and test-point variants support different cabinet and maintenance requirements.

PLC Fast Connect™

RC10/RC20 cable families connect MBS bases using flying leads, a controller-specific adapter or, for supported systems, a direct front-connector cable. Confirm connector pinout, channel count, logic and cable length for the exact I/O card.

See the PLC Fast Connect guide →

Common electrical limits

Current MBS16BIOP documentation specifies 5–32 VDC on the logic side, up to 250 VAC/DC on the field side, 8 A maximum continuous contact current and at least 4600 VAC rms I/O breakdown voltage. These base limits do not replace the selected relay’s own limits.

Thermal and protection review

Do not stop after the part-number match

✓

Ambient and derating: use the relay’s temperature curve. Current output-relay datasheets derate permitted continuous load above +30 °C.

✓

Relay bank: check the additional long-duration bank-loading rule and whether spacing changes it.

✓

Mounting: follow the datasheet recommendation for horizontal DIN-rail installation and cooling.

✓

Short circuit and overload: choose a fast fuse suited to both load and relay; verify its real protective coordination.

✓

Off state: confirm leakage current and voltage drop are acceptable to the load or controller input.

✓

Approvals: verify the exact relay-and-socket combination for UL, ATEX/IECEx or other project requirements.

Information for final selection

Send these details with your application request

1

Controller: manufacturer, CPU/remote-I/O system, exact I/O card and PNP/NPN or sourcing/sinking logic.

2

Signal direction: field-to-input or output-to-load, plus required normal and fault state.

3

Voltage: AC/DC, nominal range, tolerances, polarity and frequency where applicable.

4

Device data: sensor leakage and cable capacitance, or load current, inrush and L/R.

5

Duty: switching frequency, on-time, release-time requirement and expected lifetime.

6

Installation: channel count, ambient temperature, mounting, terminal preference, approvals and cable route.

Frequently asked questions

PLC/DCS relay-selection basics

What is the difference between an input relay and an output relay?

An input relay receives a field-side signal and provides an isolated signal to a PLC or DCS input. An output relay receives the controller command and switches a field-side load. Reversing the direction changes both the electrical specification and the socket wiring.

Can I select an output relay from continuous current only?

No. Check load voltage, AC/DC type, inrush, inductive L/R, switching frequency, ambient temperature and protection. A coil or lamp can momentarily demand many times its steady current.

Why are SLI230CR and SLI230CRP not interchangeable by default?

They have different input characteristics. SLI230CRP is intended for two-wire proximity sensors and publishes a switch-off current and cable-capacitance limit. Each suffix identifies a distinct model.

When should I use an MBS base?

Use an MBS8 or MBS16 base when several channels benefit from dense mounting and a shared cable/adapter connection to the PLC or DCS. For a single or dispersed channel, an individual MIS or MOS socket may be simpler.

Does 4600 VAC isolation make every circuit compatible?

No. Isolation is only one design parameter. The interface must also meet voltage, current, threshold, timing, thermal, protection, wiring and approval requirements.

✓ Sources: current Delcon SLI24CR, SLI230CR, SLI230CRP, SLO24CR, SLO24CRA5, SLO24TR, MIS/MOS 1GN and MBS16BIOP datasheets · Draft prepared for technical review · 4 November 2026

Send us the complete I/O channel data.

Delcon can help select the relay, socket or MBS base, cable and adapter once the controller card and field device or load are known.