Engineering guide · Industrial I/O isolation

Pulse-transformer relays: how magnetic isolation works

A Delcon relay transfers a validated switching command across a galvanic isolation barrier as controlled magnetic pulses. The pulse transformer carries the command; a model-specific solid-state stage switches the actual AC, DC or PLC-input circuit.

Four-stage diagram of Delcon pulse-transformer relay operation from input validation through magnetic isolation to solid-state output switching
The isolation method transfers control information—not load power—between the input and output sides.

It is not a mechanical relay

The transformer crosses the isolation barrier, while a semiconductor selected for the real load performs the switching.

It is not an optocoupler

The command is coupled magnetically instead of being converted into light and detected through an LED-based optical channel.

The rating is always model-specific

Isolation architecture is shared, but AC, DC, high-voltage DC and PLC-input stages have different verified limits.

Quick answer

What is a pulse-transformer relay?

It is a solid-state interface relay in which the control command crosses the input/output isolation barrier through a small transformer. Delcon first evaluates the incoming signal against defined switching conditions, encodes a valid command into pulses, transfers those pulses magnetically and uses the reconstructed command to control the output stage.

Galvanic isolation means there is no direct conductive path between the control and load circuits. It does not mean that every model can switch every load. Voltage, current, inrush, load type, timing, installation and approvals still have to match the exact datasheet.

Operating principle

One switching command, four controlled stages

1

Evaluate the input

The input circuit checks whether the real signal meets the model’s specified turn-on condition. Separate turn-on and turn-off levels provide hysteresis.

2

Create pulses

Only a valid input state starts the pulse-generation circuit. Weak induced signals below the stated threshold do not become output commands.

3

Cross the barrier

The transformer couples the controlled pulses magnetically while keeping the two circuits galvanically separated.

4

Switch the output

Secondary-side electronics reconstruct the command and drive the purpose-built output stage for the selected AC, DC or PLC-input duty.

The status LED follows the output command. In the featured Delcon architecture it illuminates while the relay output is switched on, giving a useful local indication without replacing electrical measurement or controller diagnostics.

Technology comparison

Pulse transformer, optocoupler and mechanical contact solve different parts of the problem

Isolation method alone does not determine whether a relay is suitable. Compare the complete device, including its input thresholds, off-state behaviour, switching stage, protection, load ratings and lifetime.

Architecture How the command crosses the barrier Switching element Engineering considerations
Delcon pulse-transformer relay Controlled magnetic pulses through a transformer Model-specific solid-state AC, DC or low-current output Defined input behaviour, no mechanical wear and product-specific isolation, leakage, inrush and load limits.
Optocoupler-based solid-state relay Input LED emits light; detector receives it Semiconductor output stage Performance depends on LED drive, detector, thresholds, output supply and protection. Evaluate the whole relay, not the word “optical”.
Electromechanical relay Magnetic coil moves physical contacts Mechanical contact Can switch AC and DC with a contact, but contact bounce, arcing, mechanical wear, coil power and switching frequency matter.

Why the architecture matters

Designed around real industrial interface problems

Defined switching thresholds

A published turn-on level, a lower turn-off level and hysteresis make the decision boundary explicit. This is important when a long cable or electronic sensor leaves residual voltage at the input.

Low and specified leakage

A solid-state output is never an ideal dry contact. Delcon states model-specific off-state leakage so sensitive PLC inputs and low-current loads can be checked before installation.

No contact wear

There are no mechanical contacts to bounce, arc or wear during normal switching. This supports frequent operation and predictable service life within the published limits.

No arbitrary extra derating

The continuous-current value in a Delcon datasheet is the usable rating under its specified operating and installation conditions. Do not apply an invented generic reduction factor.

Purpose-built load stages

Triac and MOSFET stages are selected for different duties. An AC output is not interchangeable with a DC output, even when the control voltage is the same.

Model-specific internal protection

Depending on the relay, Delcon uses a varistor, diode or RC network to protect the switching stage. Do not add external suppression automatically; follow the exact datasheet and evaluate the real load.

Input relays and output relays

The same isolation principle serves opposite signal directions

Input relay: field signal → PLC or DCS

The input side evaluates a field voltage—such as 24 VDC, 120 VAC or 240 VAC—and the isolated low-current output presents a defined signal to the controller input. This is useful for long field wiring, electronic sensors and signal conversion.

  • Check field voltage and guaranteed on/off thresholds.
  • Check sensor off-state leakage and cable capacitance.
  • Check the relay output against the PLC input current and voltage.

Output relay: PLC or DCS → field load

The input accepts the controller command and the isolated output stage switches the field load. The relay stage is selected from the load technology, not from control voltage alone.

  • Separate AC and DC loads first.
  • Check continuous current, inrush and switching frequency.
  • For an inductive DC load, verify the model-specific L/R limit.

Product examples

One isolation architecture, different verified output duties

Model Interface duty Published example limits Starting point for selection
SLO24TR 24 VDC-controlled AC output 0–265 VAC, 3 A continuous, 90 A / 20 ms inrush AC solenoids, contactors and other loads whose inrush and duty fit the datasheet.
SLO24CRA5 24 VDC-controlled high-voltage DC output 0–380 VDC, 5 A continuous, L/R 50 ms at 24 V / 5 A Demanding DC and inductive loads within the published limits.
SLI230CRP 240 VAC field input to PLC input 1 µA output leakage, 4,600 VAC RMS / 1 s input/output test voltage Suitable two-wire proximity sensors and long AC field circuits.
SLI24CR 24 VDC field input to PLC input 16 VDC on / 14 VDC off, 0–50 mA output, no minimum load Fast, isolated transfer of 24 VDC field signals to controller inputs.

These are examples, not a substitution table. Use the current product datasheet for final limits. A matching nominal voltage does not confirm load type, inrush capability, leakage-current compatibility, socket, cooling or approval requirements.

Engineering selection

Seven checks before specifying a pulse-transformer relay

1

Signal direction: field signal to PLC input, or controller output to field load?

2

Control signal: AC or DC, nominal range and guaranteed available current?

3

Load circuit: AC/DC voltage, continuous current and load type?

4

Switching stress: inrush amplitude and duration, L/R or other inductive data?

5

Off state: maximum acceptable leakage, residual voltage and minimum load?

6

Operation: switching frequency, ambient temperature, grouping and cooling?

7

System: socket, fusing, cable length, electrical noise and required approvals?

Frequently asked questions

Pulse-transformer relay basics

Does the pulse transformer power the field load?

No. It transfers the switching command across the galvanic barrier. The model-specific output circuit switches the actual load or controller input.

Is magnetic isolation automatically better than every optocoupler?

No single component word proves application performance. Compare the complete relays using guaranteed thresholds, isolation test values, leakage, voltage drop, load capability, temperature, protection and lifetime.

Can a pulse-transformer relay replace a mechanical relay directly?

Often it can, but it is not a universal drop-in substitution. Confirm AC or DC load type, voltage, continuous and inrush current, off-state leakage tolerance, on-state voltage drop, socket and failure behaviour.

Do Delcon output relays normally need external protective components?

Normally not when the correct Delcon relay is selected and the application remains within its datasheet limits. Internal protection is model-specific. Do not add suppression by habit; review the exact load and datasheet if release time, transients or unusual wiring are involved.

Does every Delcon relay have the same isolation and load rating?

No. Values are model-specific. Many featured plug-in products specify high input/output test voltage, but the exact isolation, clearance, voltage, current, leakage, timing and environmental limits must be taken from the selected product’s current datasheet.

When is the technology especially useful?

It is particularly relevant for PLC and DCS interfaces exposed to electrical noise, long field cables, sensor leakage, frequent switching or demanding AC and DC loads—provided the chosen model covers the complete application.

✓ Sources: current Delcon Technology page and featured product datasheets · Technically reviewed and approved by Delcon Oy · 19 October 2026

Choose the relay from the real signal and load.

Send Delcon the control voltage, load type, working voltage, current, inrush, switching frequency and installation conditions.