It is not a mechanical relay
The transformer crosses the isolation barrier, while a semiconductor selected for the real load performs the switching.
Engineering guide · Industrial I/O isolation
A Delcon relay transfers a validated switching command across a galvanic isolation barrier as controlled magnetic pulses. The pulse transformer carries the command; a model-specific solid-state stage switches the actual AC, DC or PLC-input circuit.

The transformer crosses the isolation barrier, while a semiconductor selected for the real load performs the switching.
The command is coupled magnetically instead of being converted into light and detected through an LED-based optical channel.
Isolation architecture is shared, but AC, DC, high-voltage DC and PLC-input stages have different verified limits.
Quick answer
It is a solid-state interface relay in which the control command crosses the input/output isolation barrier through a small transformer. Delcon first evaluates the incoming signal against defined switching conditions, encodes a valid command into pulses, transfers those pulses magnetically and uses the reconstructed command to control the output stage.
Operating principle
The input circuit checks whether the real signal meets the model’s specified turn-on condition. Separate turn-on and turn-off levels provide hysteresis.
Only a valid input state starts the pulse-generation circuit. Weak induced signals below the stated threshold do not become output commands.
The transformer couples the controlled pulses magnetically while keeping the two circuits galvanically separated.
Secondary-side electronics reconstruct the command and drive the purpose-built output stage for the selected AC, DC or PLC-input duty.
The status LED follows the output command. In the featured Delcon architecture it illuminates while the relay output is switched on, giving a useful local indication without replacing electrical measurement or controller diagnostics.
Technology comparison
Isolation method alone does not determine whether a relay is suitable. Compare the complete device, including its input thresholds, off-state behaviour, switching stage, protection, load ratings and lifetime.
| Architecture | How the command crosses the barrier | Switching element | Engineering considerations |
|---|---|---|---|
| Delcon pulse-transformer relay | Controlled magnetic pulses through a transformer | Model-specific solid-state AC, DC or low-current output | Defined input behaviour, no mechanical wear and product-specific isolation, leakage, inrush and load limits. |
| Optocoupler-based solid-state relay | Input LED emits light; detector receives it | Semiconductor output stage | Performance depends on LED drive, detector, thresholds, output supply and protection. Evaluate the whole relay, not the word “optical”. |
| Electromechanical relay | Magnetic coil moves physical contacts | Mechanical contact | Can switch AC and DC with a contact, but contact bounce, arcing, mechanical wear, coil power and switching frequency matter. |
Why the architecture matters
A published turn-on level, a lower turn-off level and hysteresis make the decision boundary explicit. This is important when a long cable or electronic sensor leaves residual voltage at the input.
A solid-state output is never an ideal dry contact. Delcon states model-specific off-state leakage so sensitive PLC inputs and low-current loads can be checked before installation.
There are no mechanical contacts to bounce, arc or wear during normal switching. This supports frequent operation and predictable service life within the published limits.
The continuous-current value in a Delcon datasheet is the usable rating under its specified operating and installation conditions. Do not apply an invented generic reduction factor.
Triac and MOSFET stages are selected for different duties. An AC output is not interchangeable with a DC output, even when the control voltage is the same.
Depending on the relay, Delcon uses a varistor, diode or RC network to protect the switching stage. Do not add external suppression automatically; follow the exact datasheet and evaluate the real load.
Input relays and output relays
The input side evaluates a field voltage—such as 24 VDC, 120 VAC or 240 VAC—and the isolated low-current output presents a defined signal to the controller input. This is useful for long field wiring, electronic sensors and signal conversion.
The input accepts the controller command and the isolated output stage switches the field load. The relay stage is selected from the load technology, not from control voltage alone.
Product examples
| Model | Interface duty | Published example limits | Starting point for selection |
|---|---|---|---|
| SLO24TR | 24 VDC-controlled AC output | 0–265 VAC, 3 A continuous, 90 A / 20 ms inrush | AC solenoids, contactors and other loads whose inrush and duty fit the datasheet. |
| SLO24CRA5 | 24 VDC-controlled high-voltage DC output | 0–380 VDC, 5 A continuous, L/R 50 ms at 24 V / 5 A | Demanding DC and inductive loads within the published limits. |
| SLI230CRP | 240 VAC field input to PLC input | 1 µA output leakage, 4,600 VAC RMS / 1 s input/output test voltage | Suitable two-wire proximity sensors and long AC field circuits. |
| SLI24CR | 24 VDC field input to PLC input | 16 VDC on / 14 VDC off, 0–50 mA output, no minimum load | Fast, isolated transfer of 24 VDC field signals to controller inputs. |
These are examples, not a substitution table. Use the current product datasheet for final limits. A matching nominal voltage does not confirm load type, inrush capability, leakage-current compatibility, socket, cooling or approval requirements.
Engineering selection
Signal direction: field signal to PLC input, or controller output to field load?
Control signal: AC or DC, nominal range and guaranteed available current?
Load circuit: AC/DC voltage, continuous current and load type?
Switching stress: inrush amplitude and duration, L/R or other inductive data?
Off state: maximum acceptable leakage, residual voltage and minimum load?
Operation: switching frequency, ambient temperature, grouping and cooling?
System: socket, fusing, cable length, electrical noise and required approvals?
Frequently asked questions
No. It transfers the switching command across the galvanic barrier. The model-specific output circuit switches the actual load or controller input.
No single component word proves application performance. Compare the complete relays using guaranteed thresholds, isolation test values, leakage, voltage drop, load capability, temperature, protection and lifetime.
Often it can, but it is not a universal drop-in substitution. Confirm AC or DC load type, voltage, continuous and inrush current, off-state leakage tolerance, on-state voltage drop, socket and failure behaviour.
Normally not when the correct Delcon relay is selected and the application remains within its datasheet limits. Internal protection is model-specific. Do not add suppression by habit; review the exact load and datasheet if release time, transients or unusual wiring are involved.
No. Values are model-specific. Many featured plug-in products specify high input/output test voltage, but the exact isolation, clearance, voltage, current, leakage, timing and environmental limits must be taken from the selected product’s current datasheet.
It is particularly relevant for PLC and DCS interfaces exposed to electrical noise, long field cables, sensor leakage, frequent switching or demanding AC and DC loads—provided the chosen model covers the complete application.
Continue your engineering review
Send Delcon the control voltage, load type, working voltage, current, inrush, switching frequency and installation conditions.