SLI230CR
Used between sensors/switches & PLC for:
- Isolation (4600VAC rms)
- Voltage adapting (normally 230VAC to 24VDC)
- As a noise filter to prevent malfunction due to cable capacitance, long parallel signal cables or other sources of noise
Datasheet
3D files

This relay has
17 years
MTTF (Mean Time To Failure)Primary
Input voltage | nominal | nominal | 220...240 |
Input current at nominal voltage | typical | typical | 4,6 |
Input current at nominal voltage | maximum | maximum | 5 |
Input voltage range | minimum | minimum | 190 |
Input voltage range | maximum | maximum | 265 |
Input impedance | typical | typical | 50 |
Switch-on voltage | typical | typical | 170 |
Switch-on voltage | maximum | maximum | 190 |
Switch-off voltage | typical | typical | 110 |
Switch-off voltage | minimum | minimum | 80 |
Secondary
Load voltage | minimum | minimum | 0 |
Load voltage | maximum | maximum | 60 |
Load current | maximum | maximum | 50 |
Voltage drop at maximum load | typical | typical | 0,2 |
Voltage drop at maximum load | maximum | maximum | 0,4 |
Switch-on delay | typical | typical | 50 |
Switch-off delay | typical | typical | 50 |
Leakage current (off-state) | maximum | maximum | 1 |