SLO12TR
SL-series plug-in output relay, 1NO 3A (90A/20ms)/240VAC
Application:
-
Interface relay between PLC and field apparatus
-
Control of pumps, solenoids, fans, contactors etc.
-
Suitable for both resistive and inductive AC-loads
-
if required operation temperature range is below -10 °C then select type SLO 24TH
DelconRelay benefits comparing to electromechanical relays and optos:
- Works from zero loads upwards --> no minimum load requirement
- Extremely low leakage current
- Built in suppression circuits on a signal sides to ensure that they work correctly in industrial areas with high interference levels originated by cable capacitance
- Built-in protection (varistor, diode, RC-circuit etc.) for the switching component to extend reliability and life time even more
- 100 % clear status indication, LED is synchronised with the output
- Breakdown voltage Input/Output 4600VAC rms
- 10 year warranty
Datasheet
3D files

This relay has
365,3 years
MTTF (Mean Time To Failure)Primary
Input voltage | nominal | nominal | 12 |
Input current | typical | typical | 12 |
Input current | maximum | maximum | 15 |
Input voltage range | minimum | minimum | 9 |
Input voltage range | maximum | maximum | 18 |
Input impedance | typical | typical | 1 |
Switch-on voltage | typical | typical | 8 |
Switch-on voltage | maximum | maximum | 9 |
Switch-off voltage | typical | typical | 7 |
Switch-off voltage | minimum | minimum | 6 |
Secondary
Load voltage | minimum | minimum | 0 |
Load voltage | nominal | nominal | 240 |
Load voltage | maximum | maximum | 265 |
Load current | maximum | maximum | 3 |
Load current 20 ms | maximum | maximum | 90 |
Voltage drop at maximum load | typical | typical | 1 |
Switch-on delay | typical | typical | 0,5 |
Switch-on delay | maximum | maximum | 1 |
Switch-off delay | typical | typical | - |
Switch-off delay | maximum | maximum | 11 |
Load inductance at 240 VAC 3 A | range | range | 0...1 |
Leakage current (off-state) | typical | typical | 1,5 |
dv/dt, off-state | typical | typical | 200 |