SLO24CRAI
For inductive loads and high DC voltages.
Normally closed function.
Application e.g. all type of DC-loads.
Main benefits comparing to electromechanical relays and opto coupled relays:
- No limited lifetime even with difficult loads, 10 year warranty
- Handles inductive loads and high DC-loads without extra protection elements
- High tolerance against noises
- Guaranteed switching on- and off-levels
- 100 % clear status indication
- Relatively high transient protection
- Extreme reliability
- No need for over dimension of the relay, all values are effective values
- No minimum load requirement
Datasheet
3D files

This relay has
70,8 years
MTTF (Mean Time To Failure)Primary
Input voltage | nominal | nominal | 24 |
Input current | typical | typical | 9 |
Input current | maximum | maximum | 10 |
Input voltage range | minimum | minimum | 16 |
Input voltage range | maximum | maximum | 32 |
Input impedance | typical | typical | 2,4 |
Switch-on voltage | typical | typical | 15 |
Switch-on voltage | maximum | maximum | 16 |
Switch-off voltage | typical | typical | 12 |
Switch-off voltage | minimum | minimum | 10 |
Secondary
Load voltage | minimum | minimum | 0 |
Load voltage | nominal | nominal | 250 |
Load voltage | maximum | maximum | 300 |
Load current | maximum | maximum | 1,8 |
Voltage drop at maximum load | typical | typical | 0,4 |
Switch-on delay | typical | typical | 0,5 |
Switch-on delay | maximum | maximum | 1 |
Switch-off delay | typical | typical | 0,5 |
Switch-off delay | maximum | maximum | 1 |
Load inductance at 250 V 1,8 A, L/R | maximum | maximum | 10 |
Load inductance at 24 V 1,8 A, L/R | maximum | maximum | 100 |
Leakage current (off-state) | maximum | maximum | 1 |