SLO5CRA
SL-series plug-in relay, 1 NO 1,8A (12A/10 ms)/250 VDC
- For inductive loads and high DC voltages.
Application:
- Control of solenoid valves
- High DC voltage applications such as:
- Power network control equipment
- Control systems for hydroelectric generators
DelconRelay benefits comparing to electromechanical relays and optos:
- Works from zero loads upwards --> no minimum load requirement
- Extremely low leakage current
- Built in suppression circuits on a signal sides to ensure that they work correctly in industrial areas with high interference levels originated by cable capacitance
- Built-in protection (varistor, diode, RC-circuit etc.) for the switching component to extend reliability and life time even more
- 100 % clear status indication, LED is synchronised with the output
- Breakdown voltage Input/Output 4600VAC rms
- 10 year warranty
Datasheet
3D files

This relay has
70,8 years
MTTF (Mean Time To Failure)Primary
Input voltage | nominal | nominal | 5 |
Input current | typical | typical | 12 |
Input current | maximum | maximum | 15 |
Input voltage range | minimum | minimum | 3 |
Input voltage range | maximum | maximum | 7 |
Input impedance | typical | typical | 0,42 |
Switch-on voltage | typical | typical | 2,7 |
Switch-on voltage | maximum | maximum | 3 |
Switch-off voltage | typical | typical | 2,5 |
Switch-off voltage | minimum | minimum | 2,0 |
Secondary
Load voltage | minimum | minimum | 0 |
Load voltage | nominal | nominal | 250 |
Load voltage | maximum | maximum | 300 |
Load current | maximum | maximum | 1,8 |
Voltage drop at maximum load | typical | typical | 1 |
Switch-on delay | typical | typical | 0,3 |
Switch-on delay | maximum | maximum | 0,5 |
Switch-off delay | typical | typical | 0,3 |
Switch-off delay | maximum | maximum | 0,5 |
Load inductance at 250 V 1,8 A, L/R | maximum | maximum | 10 |
Load inductance at 24 V 1,8 A, L/R | maximum | maximum | 100 |
Leakage current (off-state) | maximum | maximum | 1 |