1. The coil stores energy
Current creates a magnetic field. When the switch opens, the stored energy must be released through a controlled path.
Engineering guide · DC output relays
A solenoid coil, contactor or electromagnetic brake is not defined by current alone. Reliable switching requires the load voltage, steady current, inrush, L/R time constant, stored energy, suppression method and required release time to be considered together.
Current creates a magnetic field. When the switch opens, the stored energy must be released through a controlled path.
The coil opposes a rapid current change. Without suitable protection, the resulting transient can overstress the switch and surrounding electronics.
A low clamp voltage protects gently but lets current decay slowly. A higher controlled clamp can release the valve or brake faster.
Quick answer
A coil is an energy-storage component. Its current may look harmless while energised, yet turn-off can create the highest electrical stress in the circuit. The relay and suppression must survive that event repeatedly while still meeting the machine’s release-time requirement.
Three useful relationships
These equations explain why two coils with the same nominal current can behave very differently. They support engineering review; they do not replace the relay datasheet or validation of the real circuit.
Energy rises with inductance and with the square of current. Doubling current quadruples stored energy.
A larger L/R means current decays more slowly unless a suitable higher-voltage suppression path is used.
Forcing current to change rapidly creates voltage. The suppression circuit limits where that voltage can rise.
Use component tolerances, temperature-dependent coil resistance and the real supply range when calculating the worst case.
Suppression and dynamics
Every suppression method trades voltage stress against current-decay speed. The correct choice depends on the relay, coil, wiring, required response and equipment standard.
A diode can limit the turn-off voltage strongly, but the coil current circulates and decays slowly. This can lengthen solenoid, contactor or brake release and may be unacceptable for the process.
A higher controlled clamp can dissipate energy faster and shorten release time. The relay and protection device must both be rated for the resulting voltage, energy and repetition.
These methods have different leakage, polarity, voltage and lifetime characteristics. Delcon relays use model-specific protection; follow the exact product documentation.
Delcon relay comparison
The examples below are starting points for 24 VDC control. Final selection requires the current product datasheet and the real load data.
| Relay | Load range | Continuous current | Inrush capability | Published inductive capability | Typical starting point |
|---|---|---|---|---|---|
| SLO24CR | 0–66 VDC | 0–3 A | 15 A / 10 ms | L/R 5 ms at 24 V / 2 A | General DC solenoids, contactor coils and other moderate inductive loads. |
| SLO24CRA5 | 0–380 VDC | 0–5 A | 20 A / 10 ms | L/R 50 ms at 24 V / 5 A | Highly inductive loads such as demanding solenoids and electromagnetic brakes. |
| SLO24CRX | 0–32 VDC | 0–8 A | 80 A / 10 ms | L/R 2 ms at 24 V / 5 A | High-current, low-voltage loads with a comparatively short electrical time constant. |
Ratings above apply under the conditions stated in each datasheet. Do not apply an arbitrary generic derating factor, but do verify ambient temperature, mounting, wiring, switching frequency, protection and the complete load profile.
Engineering workflow
Record load voltage, current, resistance, inductance or L/R, duty cycle and supply tolerance.
Identify suppression inside the coil and elsewhere in the field circuit, including polarity.
Set maximum release time, switching frequency and permitted turn-off voltage.
Check continuous current, inrush, L/R, load voltage, thermal conditions and protection.
Measure the real waveform and mechanical response at supply and temperature extremes.
System integration
A Delcon output relay separates the controller output from the field load and switches rapidly without mechanical contacts. It does not remove the need for correct fusing, wiring, overload protection, suppression and fault analysis.
Controller: confirm PLC output voltage, current capability and diagnostic behaviour.
Field supply: include tolerance, transients, grounding and return-path faults.
Load: use hot- and cold-coil data, not only the nominal nameplate value.
Protection: coordinate fuse, wiring, relay protection and any external clamp.
Timing: measure both electrical current decay and actual mechanical release.
Safety: assess the complete machine function and applicable safety standard.
Compact high-inductance solution
For a highly inductive 24 VDC brake, the MIOS 1HI socket and SLO24CRA5 relay form a compact DIN-rail assembly. MIOS 1HI provides field-side surge suppression close to the relay, while SLO24CRA5 provides the switching capacity for demanding inductive loads.
Read the detailed MIOS 1HI + SLO24CRA5 brake-control article →
Frequently asked questions
The magnetic field stores energy while current flows. When the switch opens, the coil generates a voltage that attempts to keep the current flowing. A suitable protection path must absorb or redirect that energy.
No. Also check load voltage, cold-coil or inrush current, L/R or inductance, stored energy, switching frequency, suppression, ambient conditions and required release time.
L/R is the electrical time constant: inductance divided by resistance. A longer time constant generally means slower current decay and a more demanding turn-off event.
It can. A low-voltage flyback path lets current decay slowly. A correctly designed higher-voltage clamp can release the mechanism faster, but it increases voltage stress and must remain within the relay and load limits.
No. The coil, relay or socket may already include protection, and a diode may make release too slow. Follow the exact product documentation and engineer the complete circuit rather than adding suppression by habit.
It can replace a mechanical switching relay in many control applications when all electrical and thermal requirements are met. It is not automatically a safety relay or a complete safety function.
Continue your engineering review
With the load voltage, current, L/R or inductance, suppression and release-time requirement, Delcon can help identify the right switching solution.