Nominal load voltage | 240 V AC / 250 V DC |
Nominal input voltage | 24 V DC |
Rated load current | 1,2 A |
Special features | For both AC- and DC-loads, fast AC switching (1kH) |
MTTF (MIL-HDBK-217F) | 34 years |
Warranty | 10 years |
Input voltage max. | 32 V DC |
Switch-on voltage | 16 V DC |
Switch-off voltage | 14 V DC |
Power consumption | 360 mW |
Input impedance | 2 kΩ |
Load current range | 0 - 1,2 A, no minimum load required |
Load voltage range | 0 - 265 V AC / 0 - 300 V DC, no minimum load required |
Inrush current | 8 A, 10 ms |
Leakage current | 1 mA |
Voltage drop | 1,5 V |
Switch-on time | 0,3 ms |
Switch-off time | 0,3 ms |
Inductive load, cos Φ | 0,3...1 |
Max. switching frequency | 1 kHz |
Insulation method | Pulse transformer (an unique feature for Delcon relay compared to opto) |
Test voltage input/output | 4600 V ACrms / 1 s |
Overvoltage category | III |
Pollution degree | 2 |
Air/creepage distance I/O | 8 mm |
Conductor size, screw terminal | 2,5 mm2 |
Conductor size, spring terminal | 0,75 - 2,5 mm2 |
Operating temperature | -25 °C to +70 °C |
Weight | 40 g |
Housing material flammability | UL 94 V-0 |
Package size | 10, 50 and 100 |