SLI230CRP

AC input, DC load — 50 mA signal relay

Nominal input 240 V AC
Load voltage 24 V DC
Load current 50 mA
Warranty 10 years
MTTF 12,9 years

33,51 €

Manufacturer's recommended price. Delivery terms: EXW Nummela, Finland.

10-year warranty ISO 9001:2015

Technical specifications

Main data
Nominal input voltage 240 V AC
Nominal load voltage 24 V DC
Rated load current 50 mA
Contact type N/O, solid state
Coil type AC
Load circuit DC
EAN / GTIN 6410027190761
Application Used with 2-wire proximity sensors
General data & attachments
Datasheet (PDF) Open
3D model files Open
Relay selection tool Open

Why choose SLI230CRP

Built for a defined industrial duty

Use SLI230CRP to bring a 240 VAC field signal safely to a 24 VDC PLC input or similar low-current control load. It is especially useful where long cables, capacitive coupling and induced voltages could otherwise cause uncertain input behaviour.

Defined 160 / 140 VAC thresholds

Separate turn-on and turn-off levels provide clear switching behaviour.

80 nF cable capacitance

A published capability for long-field-cable applications.

Only 1 µA leakage

A clearly specified low off-state current on the PLC-input side.

Pulse-transformer isolation

4,600 VAC RMS / 1 s test voltage between field and controller sides.

Application guidance

Use it where its strengths matter

Suitable applications

  • 240 VAC field signals to PLC inputs
  • Long field cables with known capacitance
  • Low-current DC control inputs
  • Industrial panels requiring galvanic field/controller isolation

Check before selection

  • Use the relay for PLC inputs and similar low-current loads; maximum load current is 50 mA.
  • If switching an inductive load, install a clamp diode across the load as required by the datasheet.
  • Check cable capacitance against the 80 nF specification and verify the actual field voltage.
  • Apply thermal derating and horizontal mounting guidance for dense installations.
Delcon design advantage: the control command crosses a pulse-transformer isolation barrier. The model-specific solid-state output stage is then selected for the actual AC, DC or PLC-input duty. See how the technology works →

Complete the assembly

Verified sockets and bus bars

For multi-channel installations, Delcon PLC Fast Connect™ mounting bases, cables and PLC adapters are also described in the product datasheet.

Related products and guides

Continue your selection

Compare the closest Delcon alternatives and review the application guidance before final selection.

Frequently asked questions

SLI230CRP selection basics

What does SLI230CRP connect?

It accepts a nominal 240 VAC field signal and provides a solid-state DC output intended for PLC inputs and similar loads.

How does it help with long cables?

The datasheet specifies 80 nF cable capacitance together with 160 VAC turn-on and 140 VAC turn-off thresholds, giving the designer published limits for the field circuit.

What is the off-state leakage current?

The specified output leakage current is 1 µA. Always confirm that value against the PLC input requirements.

Can it drive an inductive load?

It is intended for PLC inputs and similar loads. If an inductive load is used, the datasheet requires a clamp diode across the load.

✓ Source: SLI230CRP datasheet · Technically reviewed by Delcon Oy · Review date: 4 October 2026

Confirm SLI230CRP against your real signal and load.

Send Delcon the voltage, current, inrush or inductive data, switching frequency and ambient conditions.

Discuss your application →