SLI24CR

DC input, DC load — 50 mA signal relay

Nominal input 24 V DC
Load voltage 24 V DC
Load current 50 mA
Warranty 10 years
MTTF 525 years

26,88 €

Manufacturer's recommended price. Delivery terms: EXW Nummela, Finland.

10-year warranty ISO 9001:2015

Technical specifications

Main data
Nominal input voltage 24 V DC
Nominal load voltage 24 V DC
Rated load current 50 mA
Contact type N/O, solid state
Coil type DC
Load circuit DC
EAN / GTIN 6410027191119
General data & attachments
Datasheet (PDF) Open
3D model files Open
Relay selection tool Open

Why choose SLI24CR

Built for a defined industrial duty

Use SLI24CR when a 24 VDC field signal must be transferred reliably to a PLC or DCS input. The output operates from 0 to 60 VDC and 0 to 50 mA with no minimum load requirement, while signal-side hysteresis provides predictable state changes.

No minimum load

The solid-state output operates from 0 to 50 mA and 0 to 60 VDC.

Only 1 µA leakage

A clearly specified low off-state current for PLC-input applications.

0.3 ms switching

Fast solid-state response without mechanical contact wear.

Pulse-transformer isolation

4,600 VAC RMS / 1 s test voltage between field and controller sides.

Application guidance

Use it where its strengths matter

Suitable applications

  • 24 VDC field signals to PLC or DCS inputs
  • Low-current DC control inputs
  • Industrial panels requiring galvanic field/controller isolation
  • Applications requiring fast, contactless signal transfer

Check before selection

  • Maximum load current is 50 mA; this relay is intended for PLC inputs and similar low-current loads.
  • If switching an inductive load, install a clamp diode across the load as required by the datasheet.
  • Verify the real signal against the 16 VDC turn-on and 14 VDC turn-off thresholds.
  • Apply the published thermal derating and horizontal-mounting guidance in dense installations.
Delcon system advantage: combine verified relays, mounting hardware and PLC connectivity as one maintainable industrial interface. See how Delcon technology works →

Complete the assembly

Related products and variants

For multi-channel installations, Delcon PLC Fast Connect™ mounting bases, cables and PLC adapters are described in the product datasheet.

Frequently asked questions

SLI24CR selection basics

What does SLI24CR connect?

It accepts a nominal 24 VDC field signal and provides a galvanically isolated solid-state DC output for PLC inputs and similar low-current loads.

Does SLI24CR require a minimum load?

No. The datasheet specifies no minimum output current and no minimum output voltage within the published 0–50 mA and 0–60 VDC ranges.

What is the off-state leakage current?

The specified output leakage current is 1 µA. Confirm that value against the PLC input requirements.

Can it drive an inductive load?

It is intended for PLC inputs and similar loads. If an inductive load is used, the datasheet requires a clamp diode across the load.

✓ Source: SLI24CR datasheet · Technically reviewed by Delcon Oy · Review date: 6 October 2026

Confirm SLI24CR against your field signal and PLC input.

Send Delcon the field voltage, load or input data, PLC and I/O-card type, cable length and installation conditions.

Discuss your application →