No minimum load
The solid-state output operates from 0 to 50 mA and 0 to 60 VDC.
DC input, DC load — 50 mA signal relay
26,88 €
Manufacturer's recommended price. Delivery terms: EXW Nummela, Finland.
Why choose SLI24CR
Use SLI24CR when a 24 VDC field signal must be transferred reliably to a PLC or DCS input. The output operates from 0 to 60 VDC and 0 to 50 mA with no minimum load requirement, while signal-side hysteresis provides predictable state changes.
The solid-state output operates from 0 to 50 mA and 0 to 60 VDC.
A clearly specified low off-state current for PLC-input applications.
Fast solid-state response without mechanical contact wear.
4,600 VAC RMS / 1 s test voltage between field and controller sides.
Application guidance
Complete the assembly
For multi-channel installations, Delcon PLC Fast Connect™ mounting bases, cables and PLC adapters are described in the product datasheet.
Engineering resources
Frequently asked questions
It accepts a nominal 24 VDC field signal and provides a galvanically isolated solid-state DC output for PLC inputs and similar low-current loads.
No. The datasheet specifies no minimum output current and no minimum output voltage within the published 0–50 mA and 0–60 VDC ranges.
The specified output leakage current is 1 µA. Confirm that value against the PLC input requirements.
It is intended for PLC inputs and similar loads. If an inductive load is used, the datasheet requires a clamp diode across the load.
Send Delcon the field voltage, load or input data, PLC and I/O-card type, cable length and installation conditions.