SLOP230TR

AC input, AC load — 1.5 A signal relay

Nominal input 240 V AC
Load voltage 240 V AC
Load current 1.5 A
Warranty 10 years
MTTF 239,7 years

38,66 €

Manufacturer's recommended price. Delivery terms: EXW Nummela, Finland.

10-year warranty ISO 9001:2015

Technical specifications

Main data
Nominal input voltage 240 V AC
Nominal load voltage 240 V AC
Rated load current 1.5 A
Contact type N/O, solid state
Coil type AC
Load circuit AC
EAN / GTIN 6410027190679
Application AC input and AC output voltages
General data & attachments
Datasheet (PDF) Open
3D model files Open
Relay selection tool Open

Why choose SLOP230TR

Built for a defined industrial duty

Use SLOP230TR when both the control signal and the switched load are nominal 240 VAC. Its contactless output avoids mechanical contact wear, while defined switching thresholds and built-in protection support reliable industrial operation.

1.5 A continuous output

Use the published rating directly within the stated operating and installation conditions.

90 A / 20 ms inrush

A high short-duration capability for demanding AC load starting peaks.

No minimum load

The 0–265 VAC and 0–1.5 A ranges do not require a dummy load.

4,600 VAC RMS isolation

Pulse-transformer isolation separates the control and load circuits.

Application guidance

Use it where its strengths matter

Suitable applications

  • 240 VAC control signals switching 240 VAC loads
  • Resistive and inductive AC loads within the published current and surge limits
  • Valves, contactors and other industrial AC control loads
  • Applications requiring frequent, contactless switching

Check before selection

  • Verify the control signal against the 170 VAC turn-on and 110 VAC turn-off thresholds.
  • Use the published 1.5 A continuous-current value directly; also follow the datasheet ambient-temperature and bank-mounting conditions.
  • Confirm that the actual surge current and duration remain within 90 A / 20 ms.
  • Use a correctly rated fast fuse and ensure adequate cooling, especially with frequent switching or bank mounting.
Delcon design advantage: the control command crosses a pulse-transformer isolation barrier instead of an optocoupler. This avoids taking switching energy from the load circuit and supports operation without a minimum load. See how Delcon technology works →

Complete the assembly

Related products and variants

For multi-channel assemblies, select the relay, mounting base, cable and PLC adapter as one verified system. Delcon can design custom cables and adapters for other PLC, DCS and remote-I/O systems.

Frequently asked questions

SLOP230TR selection basics

What control signal does SLOP230TR require?

It is designed for a nominal 240 VAC input. The datasheet specifies 170 VAC turn-on and 110 VAC turn-off thresholds.

Does it require a minimum load?

No. The datasheet specifies 0–265 VAC and 0–1.5 A load ranges with no minimum load requirement.

Can it switch inductive AC loads?

Yes, provided the real load and surge remain within the datasheet limits. The datasheet notes that the TRIAC output is indifferent to load power factor, but surge current and heat dissipation must still be checked.

Which socket should be used?

Use MOS1GN for screw terminals or MOS1CCN for spring terminals. Confirm the complete relay, socket, cooling and protection arrangement.

✓ Source: SLOP230TR datasheet · Technically reviewed by Delcon Oy · Review date: 7 October 2026

Confirm SLOP230TR against the real 240 VAC control signal and AC load.

Send Delcon the control voltage, load data, switching frequency, protection and installation conditions.