SLO24CRA5

DC input, DC load — 5 A signal relay

Nominal input 24 V DC
Load voltage 300 V DC
Load current 5 A
Warranty 10 years
MTTF 137 years

45,60 €

Manufacturer's recommended price. Delivery terms: EXW Nummela, Finland.

10-year warranty ISO 9001:2015

Technical specifications

Main data
Nominal input voltage 24 V DC
Nominal load voltage 300 V DC
Rated load current 5 A
Contact type N/O, solid state
Coil type DC
Load circuit DC
EAN / GTIN 6410027185811
Application For inductive loads and high DC voltages
General data & attachments
Datasheet (PDF) Open
3D model files Open
Relay selection tool Open

Why choose SLO24CRA5

Built for a defined industrial duty

Use SLO24CRA5 when a 24 VDC control signal must switch a higher-voltage DC circuit or a demanding inductive DC load. It is designed for applications such as DC contactors, solenoids, brakes and valves where both voltage and stored inductive energy must be considered.

Up to 380 VDC

A purpose-built high-voltage DC output stage rather than a general-purpose compromise.

Verified inductive rating

Specified up to L/R 50 ms at 24 V / 5 A.

No minimum load

The specified 0–5 A range supports low-current and full-rated DC loads.

Fast MOSFET switching

Typical 0.3 ms switch-on and switch-off times.

Application guidance

Use it where its strengths matter

Suitable applications

  • High-voltage DC circuits
  • DC contactors, solenoids and valves
  • Inductive DC loads within the published L/R limit
  • Fast, contactless DC switching

Check before selection

  • Confirm load voltage, continuous current, inrush and L/R time constant against the datasheet.
  • Use a correctly rated fast fuse for short-circuit and overload protection.
  • Apply thermal derating above +30 °C and for densely mounted relay banks.
  • Install on a horizontal DIN rail and provide the cooling required by the datasheet.
Delcon design advantage: the control command crosses a pulse-transformer isolation barrier. The model-specific solid-state output stage is then selected for the actual AC, DC or PLC-input duty. See how the technology works →

Complete the assembly

Verified sockets and bus bars

For multi-channel installations, Delcon PLC Fast Connect™ mounting bases, cables and PLC adapters are also described in the product datasheet.

Related products and guides

Continue your selection

Compare the closest Delcon alternatives and review the application guidance before final selection.

Frequently asked questions

SLO24CRA5 selection basics

What makes SLO24CRA5 suitable for high-voltage DC?

Its MOSFET output is specified for a 0–380 VDC load-voltage range and a 5 A rated load current.

Can it switch inductive loads?

Yes, within the published limits. The datasheet specifies a maximum inductive load of L/R 50 ms at 24 V / 5 A.

Does it require a minimum load?

No. The datasheet specifies no minimum load for the 0–5 A current range or 0–380 VDC voltage range.

What installation limits matter most?

Check thermal derating, relay-bank loading, horizontal mounting, fuse selection and the real load’s inrush and L/R characteristics.

✓ Source: SLO24CRA5 datasheet · Technically reviewed by Delcon Oy · Review date: 4 October 2026

Confirm SLO24CRA5 against your real signal and load.

Send Delcon the voltage, current, inrush or inductive data, switching frequency and ambient conditions.

Discuss your application →