SLO48CRA5

DC input, DC load — 5 A signal relay

Nominal input 48 V DC
Load voltage 300 V DC
Load current 5 A
Warranty 10 years
MTTF 137 years

46,10 €

Manufacturer's recommended price. Delivery terms: EXW Nummela, Finland.

10-year warranty ISO 9001:2015

Technical specifications

Main data
Nominal input voltage 48 V DC
Nominal load voltage 300 V DC
Rated load current 5 A
Contact type N/O, solid state
Coil type DC
Load circuit DC
EAN / GTIN 6410027185828
Application For inductive loads and high DC voltages
General data & attachments
Datasheet (PDF) Open
3D model files Open
Relay selection tool Open

Why choose SLO48CRA5

Built for a defined industrial duty

Use SLO48CRA5 when a nominal 48 VDC controller output must switch a DC load without mechanical contacts. The relay combines pulse-transformer isolation, no minimum load requirement and a fast solid-state output in a replaceable SL-series package.

0–380 VDC load range

No minimum load voltage is required within the published range.

5 A rated load current

A defined continuous-current rating subject to temperature and bank-mounting derating.

L/R 50 ms capability

Published at 24 V / 5 A for demanding inductive DC loads.

4,600 VAC RMS isolation

One-second input/output test voltage with 8 mm air and creepage distance.

Application guidance

Use it where its strengths matter

Suitable applications

  • High-voltage DC control circuits
  • DC contactors, solenoids and valves within the published limits
  • Inductive DC loads verified against the L/R rating
  • Applications requiring a replaceable, contactless output relay

Check before selection

  • The nominal input is 48 VDC; verify the actual controller signal against the 30 VDC turn-on and 20 VDC turn-off thresholds.
  • Rated load current is 5 A, subject to temperature, duty cycle and bank-mounting derating.
  • Confirm inductive energy and surge current against the 20 A / 10 ms limit and use suitable suppression.
  • Use a correctly rated fast fuse and follow the datasheet cooling and horizontal-rail guidance.
Delcon design advantage: the control command crosses a pulse-transformer isolation barrier instead of an optocoupler. See how Delcon technology works →

Complete the assembly

Related products and variants

For multi-channel assemblies, select the mounting base, relay, cable and PLC adapter as one verified system. Delcon can also design custom cables and adapters for other PLC, DCS and remote-I/O systems.

Frequently asked questions

SLO48CRA5 selection basics

What control signal does SLO48CRA5 require?

It is designed for a nominal 48 VDC input. The datasheet specifies 30 VDC turn-on and 20 VDC turn-off thresholds.

Can it switch inductive DC loads?

Yes, within the published limits. The datasheet specifies a maximum inductive load of L/R 50 ms at 24 V / 5 A; the real load, surge and suppression still need to be verified.

Does it require a minimum load?

No. The datasheet specifies 0–380 VDC and 0–5 A load ranges with no minimum load requirement.

Which socket should be used?

Use MOS1GN for screw terminals or MOS1CCN for spring terminals. Confirm the complete relay, socket, cooling and protection arrangement.